2011-07-11 15:43:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. DESIGN PRESSURES WERE NOT SPECIFIED. A TABLE WAS
 PROVIDED, BUT THIS PARCEL IS LOCATED IN EXPOSURE C.
 THEREFORE, THE FACTORS IN FBC RESIDENTIAL R 301.2(3)
 ARE TO BE APPLIED. DESIGN PRESSURES WILL EXCEED
 +-40PSF. PLEASE REVISE INSTALLATION SCHEDULE.
  
 2. BOTTOM SUBSTRATE AND SIDE SUBSTRATES (FOR HORIZONTAL
 INSTALLATIONS) ARE MASONRY (FILLED CELLS). CONCRETE
 SPECIFIED ON INSTALLATION SCHEDULE. EITHER REVISE OR
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THE SUBSTRATE IS CONCRETE. PLEASE REVISE
 INSTALLATION SCHEDULE.
  
 3. SEE OPENING 4, 114" OPENINGS INSTALLED HORIZONTALLY
 WITH A 3.5" EDGE DISTANCE EXCEEDS 10'. THIS IS NOT
 PERMITTED IN THE PRODUCT APPROVAL. PLEASE ADDRESS.
  
 AN ATTEMPT WAS MADE TO REDLINE THE INSTALLATION
 SCHEDULE, BUT IT IS NOT CLEAR WHETHER OR NOT THIS
 PRODUCT COMPLIES WITH THE REQUIREMENTS OF THE SITE/WIND
 RESISTANCE.
  