2011-07-11 15:43:45 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. DESIGN PRESSURES WERE NOT SPECIFIED. A TABLE WAS | | PROVIDED, BUT THIS PARCEL IS LOCATED IN EXPOSURE C. | | THEREFORE, THE FACTORS IN FBC RESIDENTIAL R 301.2(3) | | ARE TO BE APPLIED. DESIGN PRESSURES WILL EXCEED | | +-40PSF. PLEASE REVISE INSTALLATION SCHEDULE. | | | | 2. BOTTOM SUBSTRATE AND SIDE SUBSTRATES (FOR HORIZONTAL | | INSTALLATIONS) ARE MASONRY (FILLED CELLS). CONCRETE | | SPECIFIED ON INSTALLATION SCHEDULE. EITHER REVISE OR | | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED | | THAT THE SUBSTRATE IS CONCRETE. PLEASE REVISE | | INSTALLATION SCHEDULE. | | | | 3. SEE OPENING 4, 114" OPENINGS INSTALLED HORIZONTALLY | | WITH A 3.5" EDGE DISTANCE EXCEEDS 10'. THIS IS NOT | | PERMITTED IN THE PRODUCT APPROVAL. PLEASE ADDRESS. | | | | AN ATTEMPT WAS MADE TO REDLINE THE INSTALLATION | | SCHEDULE, BUT IT IS NOT CLEAR WHETHER OR NOT THIS | | PRODUCT COMPLIES WITH THE REQUIREMENTS OF THE SITE/WIND | | RESISTANCE. | | |
|