Plan Review Notes For Permit 11060651 |
Permit Number |
11060651 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-06-27 12:08:11 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. TWO COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED. | | PLEASE BE ADVISED THAT, IF TWO SETS ARE NOT SUBMITTED, | | ADDITIONAL FEES WILL BE CHARGED. | | | | 2. DIRECT MOUNT PROPOSED; THE NAMING CONVENTION SHOULD | | CORRELAT WITH THE ANCHOR CHARTS ON PAGE 7. IT APPEARS | | THAT THIS IS SECTION 1. | | | | 3. PANEL MATES ARE PROPOSED AS FASTENER, PLEASE ADVISE | | AS TO WHERE THIS IS LOCATED IN THE PRODUCT APPROVAL. | | | | 4. NO EDGE DISTANCE OR SHUTTER GLASS SEPARATION | | INFORMATION WAS PROVIDED. PLEASE REVISE THE FORM. | | PLEASE ALSO SEE THE CHART ON SHEET 7; EDGE DISTANCE | | LESS THAN 3 1/2" REQUIRES A FACTOR TO BE APPLIED TO THE | | ANCHOR SPACING IN THE CHARTS. | | | | |
|