Plan Review Notes
Plan Review Notes For Permit 11060441
Permit Number 11060441
Review Stop E
Sequence Number 1
Notes
Date Text
2011-07-19 16:49:34REQUIRES ELECTRICAL SCHEMATIC SHOWING BRANCH CIRCUITS,
 DISCONNECTS, CIRCUITRY, EQUIPMENT GROUNDING, GFCI
 PROTECTION. NEC 680.21
 GENERAL PURPOSE GFCI RECEPTACLE REQUIRED FOR SERVICE.
 NEC 680.22
  