Plan Review Notes
Plan Review Notes For Permit 11060362
Permit Number 11060362
Review Stop B
Sequence Number 1
Notes
Date Text
2011-06-20 14:06:59****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS.
 NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING
 SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR
 OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 2. THE 36 3/4" X 76 3/4" WINDOW EXCEEDS MAX WINDOW SIZE
 FOR BOTH THE FIXED WINDOW AND THE HORIZONTAL ROLLER.
 SPECIFY WINDOW TYPE AND ADDRESS SIZE ISSUE. FBC 106.
  
  
  
  