2011-06-20 15:09:53BUILDING PLAN REVIEW
 PERMIT: 11060309
 ADD: 2201 45 TH ST
 CONT: WESTBROOKE
 TEL: (561)239-7133
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THERE SEEMS TO BE A DISCREPANCY IN THE USE OF DOOR
 SYMBOLS FOUND ON SHEET A-001, THE DIFFERENCE BETWEEN
 EXISSTING DOORS AND NEW DOORS AS FOUND
 ON SHEET A-112. THE DOORS IN QUESTION WILL BE DOOR 101
 THE ELECTRIC ROOM WHICH IS INDICATED AS 1 HOUR WALL
 RATINGS BUT THE DOOR DOES NOT SHOW ANY FIRE RATING ON
 SHEET A303.
  
 2) THE ROOM 103 IS INDICATED AS 1 HR WALLS BUT THE DOOR
 SCHEDULE FOUND ON A-303 THE FIRE RATING FOR DOOR 103 IS
 BLANK. THE SAME ISSUE WITH DOOR 104A.
  
 3) ROOM 111 SOILED HOLD WALL TYPE IS INDICATED AS 16-B
 BUT NO WALL TYPE IS FOUND ON SHEET A-300 .
  
 4) ROOM 126 IS VINDICATED AS A 1HOUR RATED WALL SYSTEM,
 THE DOOR SYMBOL INDICATES THIS TO BE A NEW DOOR WHERE
 AS THE DOOR SCHEDULE INDICATES THIS TO BE EXISTING,
 DISCREPANCY NO FIRE RATING IS PROVIDED.
  
  
  
  
  