Plan Review Notes
Plan Review Notes For Permit 11060279
Permit Number 11060279
Review Stop P
Sequence Number 1
Notes
Date Text
2011-06-30 16:04:002009 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO SETS OF TDH CALCULATIONS FOR THE SYSTEM.
 THE PUMP CURVE FOR THE HAYWARD SPP3010X15AZ PUMP
 SPECIFIED ON THE PLANS HAS A MAXIMUM FLOW RATE OF 100
 GPM. WHEN TDH CALCULATIONS ARE NOT SUBMITTED THE
 MAXIMUM FLOW RATE IS USED TO DETERMINE THE WATER
 VELOCITY. AT 100 GPM THE WATER VELOCITY IN 2-1/2" PIPE
 IS 6.54 FEET PER SECOND AND EXCEEDS THE 6 FEET PER
 SECOND ALLOWED IN THE BRANCH SUCTION PIPING AT THE TWO
 MAIN DRAINS. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW