Plan Review Notes For Permit 11060279 |
Permit Number |
11060279 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-06-30 16:04:00 | 2009 FBC W/2009 REVISIONS | | | | DENIED BY PLUMBING | | | | 1) SUBMIT TWO SETS OF TDH CALCULATIONS FOR THE SYSTEM. | | THE PUMP CURVE FOR THE HAYWARD SPP3010X15AZ PUMP | | SPECIFIED ON THE PLANS HAS A MAXIMUM FLOW RATE OF 100 | | GPM. WHEN TDH CALCULATIONS ARE NOT SUBMITTED THE | | MAXIMUM FLOW RATE IS USED TO DETERMINE THE WATER | | VELOCITY. AT 100 GPM THE WATER VELOCITY IN 2-1/2" PIPE | | IS 6.54 FEET PER SECOND AND EXCEEDS THE 6 FEET PER | | SECOND ALLOWED IN THE BRANCH SUCTION PIPING AT THE TWO | | MAIN DRAINS. PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|