Plan Review Notes For Permit 11060218 |
Permit Number |
11060218 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-06-10 10:24:20 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. THIS BUILDING EXCEEDS 3 STORIES, OUTSIDE SCOPE FOR | | CBC, SEE FS489. THE COMPONENTS & CLADDING ARE SUBJECT | | TO WIND LOADS. | | | | 2. DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE | | REQUIRED TO BE DESIGNED USING ASCE7, FBC1609.1.1. | | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | PUBLIC RECORD ARE TO BE SIGNED SEALED ORIGINALS | | FAC61G15-23.002. |
|