2011-06-23 12:22:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE OPENINGS 1 & 2, 4.1" SPACING REQUIRED FOR BLOCK
 SUBSTRATE, TAPCON, C2 CONNECTION TYPE, 47PSF, SPAN
 BETWEEN 6-9', PLEASE REVISE INSTALLATION SCHEDULE, FBC
 R301.
  
 2. SEE OPENING 3, C4 CONNECTION NOT PERMITTED FOR
 TAPCON INTO BLOCK SUBSTRATE. PLEASE REVISE INSTALLATION
 SCHEDULE FBC R 301.