2011-06-08 08:52:04FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE 2009 PROPERTY APPRAISER AERIAL OF THE SITE SHOWS
 A FENCE AND A TREE IN THE AREA OF THE PROPOSED
 GENERATOR. NEITHER OF THESE ARE SHOWN ON THE SUBMITTED
 SURVEY. PROVIDE A RECENT SURVEY, LESS THAN ONE YEAR
 OLD, WHICH SHOWS THE LOCATION OF THE FENCE AND THE
 LOCATION OF ANY TREES IN THE IMMEDIATE VICINITY OF THE
 PROPOSED GENERATOR.
  
 2) THE PROPOSED GENERATOR SHALL BE SHOWN ON THE NEW
 SURVEY.
  
 3) ANY TREES OR SHRUBS IMPACTED BY THE PROPOSED
 GENERATOR SHALL BE RELOCATED ON-SITE. THE RELOCATION OF
 A TREE WOULD REQUIRE THE ISSUANCE OF A TREE ALTERATION
 PERMIT BY THE PLANNING AND ZONING DEPARTMENT. IF NO
 TREES OR SHRUBS WILL BE IMPACTED, PLEASE PROVIDE A
 STATEMENT TO THAT EFFECT.
  
 4) WHERE WILL THE 500 GALLON FUEL TANK BE LOCATED? IF
 THIS TANK IS TO BE LOCATED ABOVE GROUND, THEN IT SHALL
 BE SCREENED FROM THE ADJACENT RIGHTS-OF-WAY AND THE
 NEIGHBORING PROPERTY. PROVIDE SCREENING DETAILS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.