Plan Review Notes For Permit 11060005 |
Permit Number |
11060005 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-06-13 09:35:10 | FBC 2007 FUEL GAS REVISION # 1 | | DENIED: | | | | LP TANK IS NOT SHOWN ON PLAN. | | 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP | | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF | | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, | | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY | | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK | | PER NFPA 58, TABLE 3-2.2.2. | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS | | ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF | | THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS | | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED | | PER NFPA 58 SECTION 3-2.2.7(H). | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|