Plan Review Notes
Plan Review Notes For Permit 11050497
Permit Number 11050497
Review Stop P
Sequence Number 2
Notes
Date Text
2011-07-11 15:40:252007 FBC W/2009 REVISIONS
  
 2ND REVIEW
 DENIED BY PLUMBING
  
 1) THE SECOND FLOOR BATH ROOM IS NOT VENTED CORECTLY.
 FBC R3108.2 ONLY ALLOWS ONE WET-VENTED FIXTURE DRAIN TO
 DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN
 CONNECTION. * STILL INCORRECT. THE LAVATORY DRAIN AND
 VENT NEEDS TO TIE INTO BUILDING DRAIN BETWEEN THE TUB
 AND WATER CLOSET.
  
 2) ADDRESSED.
  
 3) ADDRESSED.
  
 4) ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  