2011-07-12 13:44:46PROVISO:
  
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
 INDIVIDUAL SERVICE WIRE SIZE MUST BE #3 FOR 100
 AMPERES. NEC T 310.16
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
 MAINTAIN REQUIRED SAFETY AND ACCESS CLEARANCES FOR
 ELECTRIC PANEL BOARDS. NEC 110.26
  
  
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER