Plan Review Notes For Permit 11050497 |
Permit Number |
11050497 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-07-12 13:44:46 | PROVISO: | | | | PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE | | GROUND. NEC 250.94 | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 | | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 | | INDIVIDUAL SERVICE WIRE SIZE MUST BE #3 FOR 100 | | AMPERES. NEC T 310.16 | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE | | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A | | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | R313 | | MAINTAIN REQUIRED SAFETY AND ACCESS CLEARANCES FOR | | ELECTRIC PANEL BOARDS. NEC 110.26 | | | | | | | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | | | | | | | |
|