2011-07-12 11:44:07 | 2007 FBC W/2009 REVISIONS |
| |
| 2ND REVIEW |
| DENIED BY BUILDING |
| |
| 1) ADDRESSED. |
| |
| 2) ADDRESSED. |
| |
| 3) SPECIFY THE ONE HOUR FIRE-RESISTANCE RATED |
| FLOOR/CEILING TESTED ASSEMBLY THAT WILL BE INSTALLED. |
| PROVIDE A SECTION DETAIL OF THE TESTED ASSEMBLY WITH |
| THE FILE OR LISTING NUMBER. FBC R 317. * THE SEPARATE |
| DRAWING THAT WAS SUBMITTED (ASSEMBLY WS6-1.5) IS FOR A |
| 2 X 6 WOOD WALL ASSEMBLY. THE PLANS SPECIFY 2 X 4 WALLS |
| AND A ONE HOUR FIRE RATED 2 X 6 FLOOR/CEILING ASSEMBLY |
| IS REQUIRED. |
| |
| 4) SHOW COMPLIANCE WITH FBC R317.1.1 SUPPORTING |
| CONSTRUCTION WHICH REQUIRES THE WALLS SUPPORTING THE |
| ONE HOUR FIRE-RESISTANCE RATED FLOOR/CEILING TO HAVE AN |
| EQUAL OR GREATER FIRE-RESISTIVE RATING. PROVIDE A |
| SECTION DETAIL OF THE TESTED ASSEMBLY WITH THE FILE OR |
| LISTING NUMBER. * THE UL DESIGN SPECIFIED ON THE PLANS |
| ( DESIGN NUMBER U 448 ) IS FOR A NON- BEARING STEEL |
| STUD WALL. THE PLANS AND YOUR SPAN CALCULATIONS |
| INDICATE TWO INTERIOR BEARING WOOD FRAME WALLS WITH 2 X |
| 4 STUDS 24" O.C. |
| |
| 5) ADDRESSED. |
| |
| 6) SHOW COMPLIANCE WITH FBC R602.1.2 FOR THE FIRE |
| BLOCKING THAT IS REQUIRED IN THE BALLOON FRAMED WALLS |
| AT THE CEILING AND FLOOR LEVELS. * THE FIREBLOCKING IS |
| REQUIRED AT THE CEILING OF THE FIRST FLOOR UNIT AND AT |
| THE FLOOR OF THE SECOND FLOOR UNIT. |
| |
| 7) ADDRESSED. |
| |
| 8) ADDRESSED. PLANS AND CALCULATIONS INDICATE TWO |
| INTERIOR BEARING WALLS. |
| |
| 9) THE STAIRWAYS AND HANDRAILS ARE REQUIRED TO COMPLY |
| WITH FBC R311.5. THE PLANS SITE SBC 1608.2.1 AND 1007 |
| WHICH NO LONGER APPLY. CORRECT SHEET A-3. NOT |
| ADDRESSED. |
| |
| 10) ADDRESSED. |
| |
| 11) ADDRESSED. |
| |
| 12) THE PLANS INDICATE A NEW EXTERIOR DOOR INSTALLED ON |
| THE LAUNDRY ROOM. SUBMIT TWO COPIES OF PRODUCT |
| APPROVALS FOR THE DOOR AS REQUIRED BY DCA RULE 9N-3. * |
| THE PRODUCT APPROVAL MIAMI-DADE NOA THAT WAS SUBMITED |
| IS FOR AN OUTSWING DOOR AND THE FILE HAS BEEN CLOSED |
| AND IS NO LONGER VALID. SUBMIT TWO COPIES OF A CURRENT |
| PRODUCT APPROVAL FOR THE EXTERIOR INSWING DOOR |
| SPECIFIED ON THE PLANS. |
| |
| 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| AMENDMENTS 106.3.3 * NEW DOOR PRODUCT APPROVALS WILL |
| NEED TO BE REVIEWED AND APPROVED BY DESIGNER OF RECORD. |
| |
| 14) ADDRESSED. |
| |
| 15) ADDRESSED. |
| |
| 16) ADDRESSED. |
| |
| 17) SUBMIT A RESPONSE LETTER INDICATING HOW THE REVIEW |
| COMMENTS HAVE BEEN ADDRESSED. |
| |