Plan Review Notes
Plan Review Notes For Permit 11050497
Permit Number 11050497
Review Stop B
Sequence Number 2
Notes
Date Text
2011-07-12 11:44:072007 FBC W/2009 REVISIONS
  
 2ND REVIEW
 DENIED BY BUILDING
  
 1) ADDRESSED.
  
 2) ADDRESSED.
  
 3) SPECIFY THE ONE HOUR FIRE-RESISTANCE RATED
 FLOOR/CEILING TESTED ASSEMBLY THAT WILL BE INSTALLED.
 PROVIDE A SECTION DETAIL OF THE TESTED ASSEMBLY WITH
 THE FILE OR LISTING NUMBER. FBC R 317. * THE SEPARATE
 DRAWING THAT WAS SUBMITTED (ASSEMBLY WS6-1.5) IS FOR A
 2 X 6 WOOD WALL ASSEMBLY. THE PLANS SPECIFY 2 X 4 WALLS
 AND A ONE HOUR FIRE RATED 2 X 6 FLOOR/CEILING ASSEMBLY
 IS REQUIRED.
  
 4) SHOW COMPLIANCE WITH FBC R317.1.1 SUPPORTING
 CONSTRUCTION WHICH REQUIRES THE WALLS SUPPORTING THE
 ONE HOUR FIRE-RESISTANCE RATED FLOOR/CEILING TO HAVE AN
 EQUAL OR GREATER FIRE-RESISTIVE RATING. PROVIDE A
 SECTION DETAIL OF THE TESTED ASSEMBLY WITH THE FILE OR
 LISTING NUMBER. * THE UL DESIGN SPECIFIED ON THE PLANS
 ( DESIGN NUMBER U 448 ) IS FOR A NON- BEARING STEEL
 STUD WALL. THE PLANS AND YOUR SPAN CALCULATIONS
 INDICATE TWO INTERIOR BEARING WOOD FRAME WALLS WITH 2 X
 4 STUDS 24" O.C.
  
 5) ADDRESSED.
  
 6) SHOW COMPLIANCE WITH FBC R602.1.2 FOR THE FIRE
 BLOCKING THAT IS REQUIRED IN THE BALLOON FRAMED WALLS
 AT THE CEILING AND FLOOR LEVELS. * THE FIREBLOCKING IS
 REQUIRED AT THE CEILING OF THE FIRST FLOOR UNIT AND AT
 THE FLOOR OF THE SECOND FLOOR UNIT.
  
 7) ADDRESSED.
  
 8) ADDRESSED. PLANS AND CALCULATIONS INDICATE TWO
 INTERIOR BEARING WALLS.
  
 9) THE STAIRWAYS AND HANDRAILS ARE REQUIRED TO COMPLY
 WITH FBC R311.5. THE PLANS SITE SBC 1608.2.1 AND 1007
 WHICH NO LONGER APPLY. CORRECT SHEET A-3. NOT
 ADDRESSED.
  
 10) ADDRESSED.
  
 11) ADDRESSED.
  
 12) THE PLANS INDICATE A NEW EXTERIOR DOOR INSTALLED ON
 THE LAUNDRY ROOM. SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE DOOR AS REQUIRED BY DCA RULE 9N-3. *
 THE PRODUCT APPROVAL MIAMI-DADE NOA THAT WAS SUBMITED
 IS FOR AN OUTSWING DOOR AND THE FILE HAS BEEN CLOSED
 AND IS NO LONGER VALID. SUBMIT TWO COPIES OF A CURRENT
 PRODUCT APPROVAL FOR THE EXTERIOR INSWING DOOR
 SPECIFIED ON THE PLANS.
  
 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 106.3.3 * NEW DOOR PRODUCT APPROVALS WILL
 NEED TO BE REVIEWED AND APPROVED BY DESIGNER OF RECORD.
  
 14) ADDRESSED.
  
 15) ADDRESSED.
  
 16) ADDRESSED.
  
 17) SUBMIT A RESPONSE LETTER INDICATING HOW THE REVIEW
 COMMENTS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]