Notes |
Date |
Text |
2011-06-09 08:42:55 | 2007 FBC W/2009 REVISIONS | | 2008 NEC | | | | DENIED BY ELECTRIC | | | | 1) SUBMIT LOAD CALCULATIONS FOR THE SERVICE TO VERIFY | | THAT THE #1 WIRE SIZE IS ADEQUATE. ART. 215.5 & 220.40 | | | | 2) MATCH PANELS TO SERVICE RISER. THE RISER SHOWS THREE | | METER CANS LABELED 'D', 'C', 'E' AND THE ELECTRICAL | | FLOOR PLAN SHOWS 2 METERS AND DISCONNECTS AND THREE | | PANELS LABELED 'A', 'B', 'C'. ART. 110.22(A) | | | | 3) PROVIDE A PANEL SCHEDULE ON THE PLANS FOR THE 60 AMP | | PANEL OFF OF METER 'E'. ART408.4 | | | | 4) ALL OUTLETS ARE REQUIRED TO BE TAMPER RESISTANT. | | ART. 406.11 | | | | 5) ALL 15 AND 20 AMP BRANCH CIRCUITS ARE REQUIRED TO BE | | ARC FAULT PROTECTED EXCEPT THE KITCHEN, BATH ROOM AND | | OUTSIDE. ART. 210.12 | | | | 6) AT LEAST ONE GFCI RECEPTACLE OUTLET IS REQUIRED AT | | THE FRONT AND BACK OF THE DWELLING. ART. 210.52(E)(1) | | | | 7) PLEASE CLARIFY THAT THIS SERVICE IS ONLY FOR THE TWO | | STORY RESIDENCE IDENTIFIED ON THE SITE PLAN AS 423-A. | | IS THERE A SEPARATE SERVICE FOR THE OTHER TWO STORY | | RESIDENCE IDENTIFIED AS #423 ON THE SITE PLAN. ART. | | 215.5 | | | | 8) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE | | REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|