Plan Review Notes
Plan Review Notes For Permit 11050408
Permit Number 11050408
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-05-25 11:04:48222 LAKEVIEW AVENUE, 16TH FLOOR, SUITE #200
 PERMIT #11050408
 EXPIRED PERMIT #09090134
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 JOB VALUE NOT PROVIDED ON PERMIT APPLICATION. DRAWINGS
 REQUIRE ENGINEER'S SEAL IF JOB VALUE EXCEEDS $5000.
  
 THE PERMIT APPLICATION INDICATES THE WORK IS BEING
 PERFORMED ON THE 16TH FLOOR; THE PLANS INDICATE SUITE
 200.
  
 DRAWINGS DO NOT INDICATE THE PROJECT ADDRESS.
  
 THE HATCHING PATTERN SCOPE OF WORK ON THE RISER DIAGRAM
 APPEARS LIMITED WHEN COMPARED TO THE DEVICES SHOWN ON
 THE FLOOR PLAN.
  
 THE FLOOR PLAN HAS A LAYERING ISSUE AS SOME APPLIANCES
 ARE LOCATED ON OR ADJACENT TO OTHER APPLIANCES AND THE
 SCALE OF THE OBJECTS DIFFER.
  
 DUCT SMOKE DETECTORS SHALL ACTIVATE A GENERAL FIRE
 ALARM CONDITION PER LOCAL CODE AMENDMENTS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  