Plan Review Notes For Permit 11050408 |
Permit Number |
11050408 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-05-25 11:04:48 | 222 LAKEVIEW AVENUE, 16TH FLOOR, SUITE #200 | | PERMIT #11050408 | | EXPIRED PERMIT #09090134 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | JOB VALUE NOT PROVIDED ON PERMIT APPLICATION. DRAWINGS | | REQUIRE ENGINEER'S SEAL IF JOB VALUE EXCEEDS $5000. | | | | THE PERMIT APPLICATION INDICATES THE WORK IS BEING | | PERFORMED ON THE 16TH FLOOR; THE PLANS INDICATE SUITE | | 200. | | | | DRAWINGS DO NOT INDICATE THE PROJECT ADDRESS. | | | | THE HATCHING PATTERN SCOPE OF WORK ON THE RISER DIAGRAM | | APPEARS LIMITED WHEN COMPARED TO THE DEVICES SHOWN ON | | THE FLOOR PLAN. | | | | THE FLOOR PLAN HAS A LAYERING ISSUE AS SOME APPLIANCES | | ARE LOCATED ON OR ADJACENT TO OTHER APPLIANCES AND THE | | SCALE OF THE OBJECTS DIFFER. | | | | DUCT SMOKE DETECTORS SHALL ACTIVATE A GENERAL FIRE | | ALARM CONDITION PER LOCAL CODE AMENDMENTS. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|