Plan Review Notes For Permit 11050309 |
Permit Number |
11050309 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-10-24 09:28:34 | 2007 FBC W/2009 REVISIONS | | | | 1) THE WIND LOAD ANALYSIS FOR THE MWFRS AND COMPONENT | | AND CLADDING PRESSURES FROM THE ENGINEER, THE SHAFFER | | GROUP INC. IS NOT SIGNED AND SEALED AS REQUIRED BY FS | | 471 AND FAC 61G15.23.002. SUBMIT TWO SETS OF SIGNED AND | | SEALED WIND CALCULATIONS. | | | | 2) THE AWNING RECONSTRUCTION DETAIL SK-1 FROM THE | | ENGINEER, THE SHAFFER GROUP INC. IS NOT SIGNED AND | | SEALED AS REQUIRED BY FS 471 AND FAC 61G15.23.002. | | SUBMIT TWO SETS OF SIGNED AND SEALED DRAWINGS. | | | | 3) ONE SET OF PLANS HAS HAND WRITTEN CHANGES MADE BY | | THE ARCHITECT, LEE KVARNBERG. THE OTHER SET WILL NEED | | TO BE MARKED UP TO MATCH. CITY AMENDMENTS 106.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|