2011-05-25 09:56:06REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS WITH BATTERY
 BACK UP. HOMES WHICH FEATURE GAS APPLIANCES, AN
 ATTACHED GARAGE OR A FIRE PLACE REQUIRE A CARBON
 MONOXIDE DETECTOR WITHIN TEN FEET OF EACH ROOM USED FOR
 SLEEPING. FBC R313
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE
 GROUND. NEC 250.94
 NEW RECEPTACLES MUST BE ARC FAULT CIRCUIT PROTECTED.
 NEC 210-12 (B)
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES 2 FEET OR
 MORE IN WIDTH HAVE A RECEPTACLE. NEDC 210.52
 THE PLAN SHOWS MULTIPLE ELECTRIC CIRCUITS FEEDING THE
 GARAGE. A SEPARATE DISCONNECT AND PANELBOARD IS
 REQUIRED. NEC 225-30
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER