Plan Review Notes
Plan Review Notes For Permit 11050304
Permit Number 11050304
Review Stop B
Sequence Number 3
Notes
Date Text
2011-12-27 09:28:56BUILDING PLAN REVIEW
 PERMIT: 11050304
 ADD: 1225 PALM BEACH LAKES BLVD
 CONT: CILAS CONCRETE CONSTRUCTION
 TEL: (561)252-8429
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2009 FLORIDA EXISTING BUILDING CODE / 2009 SUPPLEMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SHEET A-1 INDICATES NEW PLAY AREA PLEASE PROVIDE THE
 FOLLOWING INFORMATION REQUIRED BY 2007 FBC-B
 106.3.5.1.1:
 2A)COMPLIED.
 2B) COMPLIED- BUILDING NOT SPRIVKLERED.
 2C) COMPLIED.
 2D) SEMI-COMPLIED. FLOOR PLAN/ LIFE SAFETY PLAN/ EGRESS
 INCLUDE; OCCUPANCY LOAD/GROSS/ NET/ EXIT ACCESS & EXITS
 PLEASE PROVIDE OCCUPANT LOADS FOR THE ROOMS AND
 INCIDENTAL USE AREAS INDICATED ON SHEET #1 AND TOTAL
 LOAD.
 12/27/2011 PLANS INDICATE AN OCCUPANT LOAD BASED ON 36
 SQ FT / OCCUPANT PLEASE REVIEW TABLE 1004.1.1 DAYCARE
 20/ NET
  
 3) SEMI COMPLIED. FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS:
  
 3A) NEW EXTERIOR DOOR. PLEASE REVIEW REQUIREMENTS FOR:
 1034.1 PANIC AND FIRE EXIT HARDWARE.
 1034.1.1 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE
 WHICH RELEASES WHEN A FORCE OF NO MORE THAN 15 POUNDS
 (67 N) IS APPLIED TO THE RELEASING DEVICES IN THE
 DIRECTION OF EXIT TRAVEL. SUCH RELEASING DEVICES MAY BE
 BARS OR PANELS EXTENDING NOT LESS THAN ONE-HALF THE
 WIDTH OF THE DOOR AND PLACED AT HEIGHTS SUITABLE FOR
 THE SERVICE REQUIRED, BUT NOT LESS THAN 34 INCHES (864
 MM) NOR MORE THAN 48 INCHES (1219 MM) ABOVE THE FLOOR.
 WHENEVER PANIC HARDWARE IS USED ON A LABELED FIRE DOOR,
 THE PANIC HARDWARE SHALL BE LABELED AS FIRE EXIT
 HARDWARE.
  
 3B) NEW- EGRESS WINDOWS
  
 4) SEMI COMPLIED WILL NEED TO REVIEW PANIC & FIRE
 HARDWARE FOR ALL EXTERIOR DOORS. 106.3.3 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 NEW COMMENTS NEW CHANGE OF OCCUPANCY PLANS AND SITE
 PLAN.
  
 5-9) COMPLIED.
  
 10) NO PRODUCT APPROVAL FOR THE NEW WINDOWS IN
 CLASSROOMS COMPLYING WITH :2007/09 FBC-B 1026.4.1 EVERY
 ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2 M2) IN
 EDUCATIONAL OCCUPANCIES USED FOR CLASSROOM OR OTHER
 EDUCATIONAL PURPOSES OR NORMALLY SUBJECT TO STUDENT
 OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT OCCUPANCY, OTHER THAN BATHROOMS, IN GROUP D
 OCCUPANCIES SHALL HAVE NOT LESS THAN ONE OUTSIDE WINDOW
 FOR EMERGENCY RESCUE THAT COMPLIES WITH THE FOLLOWING:
  
 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M2) IN AREA.
  
 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
  
 11) COMPLIED.
  
 12) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE
 SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
 13) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE
 NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY
 WITH SECTION 715.3.
  
  
 14) NOT REQUIRED NO LAUNDRY!
  
 15) NORTHWEST CORRIDOR MARKED AS "NO EXIT WHICH CREATES
 A DEAD-END CORRIDOR OVER 20'-0" LONG. FBC-B 1017.3.
 DEAD END CORRIDOR CAN'T BE OVER 20'-0" IN LENGTH.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]