2011-10-19 11:14:55 | BUILDING PLAN REVIEW |
| PERMIT: 11050304 |
| ADD: 1225 PALM BEACH LAKES BLVD |
| CONT: CILAS CONCRETE CONSTRUCTION |
| TEL: (561)252-8429 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| 2009 FLORIDA EXISTING BUILDING CODE / 2009 SUPPLEMENTS |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION SCOPE OF WORK INDICATES THE |
| INFILL OF PATIO NEW MASONRY AND WINDOWS, PLEASE |
| INDICATE THIS IS A CHANGE IN OCCUPANCY!!!! |
| |
| |
| 2) SHEET A-1 INDICATES NEW PLAY AREA PLEASE PROVIDE THE |
| FOLLOWING INFORMATION REQUIRED BY 2007 FBC-B |
| 106.3.5.1.1: |
| 2A)COMPLIED. |
| 2B) SEMI-COMPLIED. MINIMUM BLDG TYPE WILL BE REQUIRED |
| SINCE THIS IS A CHANGE OF OCCUPANCY/ COMPLIED |
| SPRINKLERED- YES. |
| SHEET A-0 UNDER THE HEADING OCCUPANCY/ USE PLEASE |
| CORRECT BUILDING TYPE AS III-B PROTECTED THE B |
| DESIGNATION IS UNPROTECTED, A IS PROTECTED SEE TABLE |
| 601. |
| 2C) COMPLIED. |
| 2D) SEMI-COMPLIED. FLOOR PLAN/ LIFE SAFETY PLAN/ EGRESS |
| INCLUDE; OCCUPANCY LOAD/GROSS/ NET/ EXIT ACCESS & EXITS |
| PLEASE PROVIDE OCCUPANT LOADS FOR THE ROOMS AND |
| INCIDENTAL USE AREAS INDICATED ON SHEET #1 AND TOTAL |
| LOAD. |
| |
| 3) SEMI COMPLIED. FL BLD CODE 1609.6.2.2 COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, |
| MISSING REPORTS ARE AS FOLLOWS: NEW EXTERIOR DOOR. |
| PLEASE REVIEW REQUIREMENTS FOR: |
| 1034.1 PANIC AND FIRE EXIT HARDWARE. |
| 1034.1.1 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN |
| AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS |
| SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK |
| ONLY IF IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE |
| WHICH RELEASES WHEN A FORCE OF NO MORE THAN 15 POUNDS |
| (67 N) IS APPLIED TO THE RELEASING DEVICES IN THE |
| DIRECTION OF EXIT TRAVEL. SUCH RELEASING DEVICES MAY BE |
| BARS OR PANELS EXTENDING NOT LESS THAN ONE-HALF THE |
| WIDTH OF THE DOOR AND PLACED AT HEIGHTS SUITABLE FOR |
| THE SERVICE REQUIRED, BUT NOT LESS THAN 34 INCHES (864 |
| MM) NOR MORE THAN 48 INCHES (1219 MM) ABOVE THE FLOOR. |
| WHENEVER PANIC HARDWARE IS USED ON A LABELED FIRE DOOR, |
| THE PANIC HARDWARE SHALL BE LABELED AS FIRE EXIT |
| HARDWARE. |
| |
| 4) SEMI COMPLIED WILL NEED TO REVIEW PANIC & FIRE |
| HARDWARE FOR ALL EXTERIOR DOORS. 106.3.3 PRODUCT |
| APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| NEW COMMENTS NEW CHANGE OF OCCUPANCY PLANS AND SITE |
| PLAN. |
| |
| 5) THE LANSCAPE AND SITE PLAN WILL PROBABLY BE A |
| SEPERATE PERMIT, PLEASE NOTE ACCESSIBLE PARKING SPOTS |
| (2) AND THE PLANS INDICATING ACCESS AISLE BEHIND THE |
| ACCESSIBLE SPACE. FBC-B 11-4.6.2(1) (GRAY BOX FL |
| SPECIFIC) ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE |
| ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE SO THAT |
| USERS WILL NOT BE COMPELLED TO WALK OR WHEEL BEHIND |
| PARKED VEHICLES. |
| |
| 6) IT APPEARS THIS BUILDING WILL BE A MIXED OCCUPANCY |
| WITH DAY CARE (BABIES) AND EDUCATIONAL (KINDERGARDEN |
| AND FIRST GRADE). THE DESIGNER WILL NEED TO INDICATE |
| COMPLIANCE WITH EITHER FLC-B 508.313 OR 508.3.2 AND |
| SHOW COMPLIANCE. |
| |
| 7) DISCREPANCY IN CLASSROOM THAT IS 25'-0" WIDE (ALL |
| CLASSROOMS NOT LABELED OR IDENTIFIED) PLEASE REVIEW |
| DOOR SWING BY EXIT BY STORAGE AREA SHEET A1 VERSES LIFE |
| SAFETY SHEET. |
| ROOM NOT IDENTIFIED FOR WHAT AGE CHILDREN PLEASE REVIEW |
| 1028.3 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR |
| SHALL BE RECESSED TO PREVENT INTERFERENCE WITH CORRIDOR |
| TRAFFIC; ANY DOORS NOT RECESSED SHALL OPEN 180 DEGREES |
| (3.1 RAD) TO STOP AGAINST THE WALL. DOORS IN ANY |
| POSITION SHALL NOT REDUCE THE REQUIRED CORRIDOR WIDTH |
| BY MORE THAN ONE-HALF. |
| |
| 8) SHEET A1 WALL LEGEND INDICATES WALL TYPE 3 TO BE A |
| EXISTING 1 HOUR WALL WHERE AS DETAIL W3 INDICATES THE |
| WALL STOPPING 6 INCHES ABOVE THE CEILING. PLEASE SEE |
| WALL LEGEND |
| W4 IS AN EXISTING INTERIOR WALL WHERE AS DETAIL W4 |
| INDICATES A 1-0 HOUR RATED WALL TO THE ROOF DECK ABOVE, |
| DISCREPANCY PLEASE CORRECT. |
| |
| 9) SHEET A1 INDICATES WHAT APEARS TO BE 1-0 RATED |
| CORRIDOR BY THE WALL LEGEND BUT THERE IS A 1ST GRADE |
| CLASS IN THE MIDDLE OF THIS CORRIDOR? PLEASE PROVIDE |
| EXPLANATION. |
| 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 10) PLANS INDICATE BUILDING TO BE SPRINKLERED NOTE 5 ON |
| LS SHEET, PLEASE PROVIDE SPRINKLER PLANS, PLEASE NOTE |
| IF SPRINKLER SYSTEM IS SUPERVISED. |
| 2007/09 FBC-B 1026.4.1 EVERY ROOM OR SPACE GREATER THAN |
| 250 SQUARE FEET (23.2 M2) IN EDUCATIONAL OCCUPANCIES |
| USED FOR CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR |
| NORMALLY SUBJECT TO STUDENT OCCUPANCY AND EVERY ROOM OR |
| SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER THAN |
| BATHROOMS, IN GROUP D OCCUPANCIES SHALL HAVE NOT LESS |
| THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT |
| COMPLIES WITH THE FOLLOWING: |
| |
| 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR |
| OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH, |
| 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53 |
| M2) IN AREA. |
| |
| 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING |
| DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE |
| THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR. |
| |
| 11) 36.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE |
| SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE |
| CLOSET. |
| |
| 12) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR |
| FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE |
| SHALL BE READILY ACCESSIBLE TO THE STAFF. |
| |
| 13) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE |
| NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY |
| WITH SECTION 715.3. |
| |
| |
| 14) NOTE PLANS DO NOT INDICATE ANY AREA WHERE CLEANING |
| SUPPLIES WILL BE KEPT IN A SAME ROOM NOR IF THERE IS A |
| LAUNDRY ROOM. WATER HEATER IS ALSO MISSING FROM LS |
| PLAN. |
| 436.6.2 THE FOLLOWING ROOMS OR SPACES SHALL BE |
| SEPARATED FROM THE REMAINDER OF THE BUILDING BY FIRE |
| BARRIERS HAVING A FIRE RESISTANCE RATING OF NOT LESS |
| THAN 1 HOUR AND SHALL BE PROTECTED BY AN APPROVED |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEM. |
| |
| 1. LAUNDRIES. |
| |
| 2. MAINTENANCE SHOPS, INCLUDING WOODWORKING AND |
| PAINTING AREAS. |
| |
| 3. ROOMS OR SPACES USED FOR PROCESSING OR USE OF |
| COMBUSTIBLE SUPPLIES DEEMED HAZARDOUS BY THE BUILDING |
| OFFICIAL. |
| |
| 4. ROOMS OR SPACES USED FOR PROCESSING OR USE OF |
| HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS |
| IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS. |
| |
| EXCEPTION: FOOD PREPARATION FACILITIES PROTECTED IN |
| ACCORDANCE WITH NFPA 96 SHALL NOT BE REQUIRED TO HAVE |
| OPENINGS PROTECTED BETWEEN FOOD PREPARATION AREAS AND |
| DINING AREAS. WHERE DOMESTIC COOKING EQUIPMENT IS USED |
| FOR FOOD WARMING OR LIMITED COOKING, PROTECTION OR |
| SEGREGATION OF FOOD PREPARATION FACILITIES SHALL NOT BE |
| REQUIRED IF APPROVED BY THE BUILDING OFFICIAL. |
| |
| 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |