Plan Review Notes
Plan Review Notes For Permit 11050304
Permit Number 11050304
Review Stop B
Sequence Number 2
Notes
Date Text
2011-10-19 11:14:55BUILDING PLAN REVIEW
 PERMIT: 11050304
 ADD: 1225 PALM BEACH LAKES BLVD
 CONT: CILAS CONCRETE CONSTRUCTION
 TEL: (561)252-8429
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 2009 FLORIDA EXISTING BUILDING CODE / 2009 SUPPLEMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION SCOPE OF WORK INDICATES THE
 INFILL OF PATIO NEW MASONRY AND WINDOWS, PLEASE
 INDICATE THIS IS A CHANGE IN OCCUPANCY!!!!
  
  
 2) SHEET A-1 INDICATES NEW PLAY AREA PLEASE PROVIDE THE
 FOLLOWING INFORMATION REQUIRED BY 2007 FBC-B
 106.3.5.1.1:
 2A)COMPLIED.
 2B) SEMI-COMPLIED. MINIMUM BLDG TYPE WILL BE REQUIRED
 SINCE THIS IS A CHANGE OF OCCUPANCY/ COMPLIED
 SPRINKLERED- YES.
 SHEET A-0 UNDER THE HEADING OCCUPANCY/ USE PLEASE
 CORRECT BUILDING TYPE AS III-B PROTECTED THE B
 DESIGNATION IS UNPROTECTED, A IS PROTECTED SEE TABLE
 601.
 2C) COMPLIED.
 2D) SEMI-COMPLIED. FLOOR PLAN/ LIFE SAFETY PLAN/ EGRESS
 INCLUDE; OCCUPANCY LOAD/GROSS/ NET/ EXIT ACCESS & EXITS
 PLEASE PROVIDE OCCUPANT LOADS FOR THE ROOMS AND
 INCIDENTAL USE AREAS INDICATED ON SHEET #1 AND TOTAL
 LOAD.
  
 3) SEMI COMPLIED. FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS: NEW EXTERIOR DOOR.
 PLEASE REVIEW REQUIREMENTS FOR:
 1034.1 PANIC AND FIRE EXIT HARDWARE.
 1034.1.1 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK
 ONLY IF IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE
 WHICH RELEASES WHEN A FORCE OF NO MORE THAN 15 POUNDS
 (67 N) IS APPLIED TO THE RELEASING DEVICES IN THE
 DIRECTION OF EXIT TRAVEL. SUCH RELEASING DEVICES MAY BE
 BARS OR PANELS EXTENDING NOT LESS THAN ONE-HALF THE
 WIDTH OF THE DOOR AND PLACED AT HEIGHTS SUITABLE FOR
 THE SERVICE REQUIRED, BUT NOT LESS THAN 34 INCHES (864
 MM) NOR MORE THAN 48 INCHES (1219 MM) ABOVE THE FLOOR.
 WHENEVER PANIC HARDWARE IS USED ON A LABELED FIRE DOOR,
 THE PANIC HARDWARE SHALL BE LABELED AS FIRE EXIT
 HARDWARE.
  
 4) SEMI COMPLIED WILL NEED TO REVIEW PANIC & FIRE
 HARDWARE FOR ALL EXTERIOR DOORS. 106.3.3 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 NEW COMMENTS NEW CHANGE OF OCCUPANCY PLANS AND SITE
 PLAN.
  
 5) THE LANSCAPE AND SITE PLAN WILL PROBABLY BE A
 SEPERATE PERMIT, PLEASE NOTE ACCESSIBLE PARKING SPOTS
 (2) AND THE PLANS INDICATING ACCESS AISLE BEHIND THE
 ACCESSIBLE SPACE. FBC-B 11-4.6.2(1) (GRAY BOX FL
 SPECIFIC) ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE
 ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE SO THAT
 USERS WILL NOT BE COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES.
  
 6) IT APPEARS THIS BUILDING WILL BE A MIXED OCCUPANCY
 WITH DAY CARE (BABIES) AND EDUCATIONAL (KINDERGARDEN
 AND FIRST GRADE). THE DESIGNER WILL NEED TO INDICATE
 COMPLIANCE WITH EITHER FLC-B 508.313 OR 508.3.2 AND
 SHOW COMPLIANCE.
  
 7) DISCREPANCY IN CLASSROOM THAT IS 25'-0" WIDE (ALL
 CLASSROOMS NOT LABELED OR IDENTIFIED) PLEASE REVIEW
 DOOR SWING BY EXIT BY STORAGE AREA SHEET A1 VERSES LIFE
 SAFETY SHEET.
 ROOM NOT IDENTIFIED FOR WHAT AGE CHILDREN PLEASE REVIEW
 1028.3 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR
 SHALL BE RECESSED TO PREVENT INTERFERENCE WITH CORRIDOR
 TRAFFIC; ANY DOORS NOT RECESSED SHALL OPEN 180 DEGREES
 (3.1 RAD) TO STOP AGAINST THE WALL. DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED CORRIDOR WIDTH
 BY MORE THAN ONE-HALF.
  
 8) SHEET A1 WALL LEGEND INDICATES WALL TYPE 3 TO BE A
 EXISTING 1 HOUR WALL WHERE AS DETAIL W3 INDICATES THE
 WALL STOPPING 6 INCHES ABOVE THE CEILING. PLEASE SEE
 WALL LEGEND
 W4 IS AN EXISTING INTERIOR WALL WHERE AS DETAIL W4
 INDICATES A 1-0 HOUR RATED WALL TO THE ROOF DECK ABOVE,
 DISCREPANCY PLEASE CORRECT.
  
 9) SHEET A1 INDICATES WHAT APEARS TO BE 1-0 RATED
 CORRIDOR BY THE WALL LEGEND BUT THERE IS A 1ST GRADE
 CLASS IN THE MIDDLE OF THIS CORRIDOR? PLEASE PROVIDE
 EXPLANATION.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 10) PLANS INDICATE BUILDING TO BE SPRINKLERED NOTE 5 ON
 LS SHEET, PLEASE PROVIDE SPRINKLER PLANS, PLEASE NOTE
 IF SPRINKLER SYSTEM IS SUPERVISED.
 2007/09 FBC-B 1026.4.1 EVERY ROOM OR SPACE GREATER THAN
 250 SQUARE FEET (23.2 M2) IN EDUCATIONAL OCCUPANCIES
 USED FOR CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR
 NORMALLY SUBJECT TO STUDENT OCCUPANCY AND EVERY ROOM OR
 SPACE NORMALLY SUBJECT TO CLIENT OCCUPANCY, OTHER THAN
 BATHROOMS, IN GROUP D OCCUPANCIES SHALL HAVE NOT LESS
 THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT
 COMPLIES WITH THE FOLLOWING:
  
 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 INCHES (508 MM) IN WIDTH,
 24 INCHES (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53
 M2) IN AREA.
  
 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
  
 11) 36.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL BE
 SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE
 CLOSET.
  
 12) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE
 SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
 13) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE
 NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY
 WITH SECTION 715.3.
  
  
 14) NOTE PLANS DO NOT INDICATE ANY AREA WHERE CLEANING
 SUPPLIES WILL BE KEPT IN A SAME ROOM NOR IF THERE IS A
 LAUNDRY ROOM. WATER HEATER IS ALSO MISSING FROM LS
 PLAN.
 436.6.2 THE FOLLOWING ROOMS OR SPACES SHALL BE
 SEPARATED FROM THE REMAINDER OF THE BUILDING BY FIRE
 BARRIERS HAVING A FIRE RESISTANCE RATING OF NOT LESS
 THAN 1 HOUR AND SHALL BE PROTECTED BY AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM.
  
 1. LAUNDRIES.
  
 2. MAINTENANCE SHOPS, INCLUDING WOODWORKING AND
 PAINTING AREAS.
  
 3. ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 COMBUSTIBLE SUPPLIES DEEMED HAZARDOUS BY THE BUILDING
 OFFICIAL.
  
 4. ROOMS OR SPACES USED FOR PROCESSING OR USE OF
 HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS
 IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS.
  
 EXCEPTION: FOOD PREPARATION FACILITIES PROTECTED IN
 ACCORDANCE WITH NFPA 96 SHALL NOT BE REQUIRED TO HAVE
 OPENINGS PROTECTED BETWEEN FOOD PREPARATION AREAS AND
 DINING AREAS. WHERE DOMESTIC COOKING EQUIPMENT IS USED
 FOR FOOD WARMING OR LIMITED COOKING, PROTECTION OR
 SEGREGATION OF FOOD PREPARATION FACILITIES SHALL NOT BE
 REQUIRED IF APPROVED BY THE BUILDING OFFICIAL.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]