2011-11-03 10:23:11REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE ENGINEERED DETAIL FOR ATTACMENT OF NEW
 ROOFTOP EQUIPMENT TO BUILDING STRUCTURE PER FBC-M
 301.12.
  
 2. PAGE M-1 OUTSIDE AIR CALCULATION: TABLE INDICATES
 CALCULATIONS ARE PER FBC-M 403.3 WHILE NOTE #2
 INDICATES ASHRAE 62.1 IS USED. WHICH IS CORRECT? ONE
 METHOD OR THE OTHER SHALL BE LECTED AND ADHERED TO.
  
 3. PAGE M-1 OUTSIDE AIR CALCULATION: IF ASHRAE 62.1 IS
 ELECTED, THE VENTILATION TOTALS LISTED ARE TO ALSO
 INCLUDE AN ADDITIONAL 0.18 CFM/SF OF FLOOR AREA IN THE
 SPACES BEING VENTILATED FOR DAYCARE OCCUPANCIES. SEE
 ASHRAE 62.1 TABLE 6-1 AND BREATHING ZONE OUTDOOR
 AIRFLOW EQUATION 6-1 IN SECTION 6.2.2.1.
  
 4. PLANS INDICATE HVAC SYSTEM DESIGN BY "K.O. ENERGY
 DESIGN, LLC." THIS DOES NOT APPEAR TO BE A PROFESSIONAL
 ENGINEER OR ENGINEERING BUSINESS. PLANS MUST BE
 DESIGNED BY AN ENGINEER IN ACCORDANCE WITH FBC-B
 105.3.1.2. SYSTEM MAY NOT BE DESIGNED BY A CONTRACTOR
 BECAUSE THE BUILDING OCCUPANT LOAD EXCEEDS 100 PERSONS.
 WHILE PAGE M-1 IS SIGNED AND SEALED BY AN ENGINEER, THE
 ENGINEER IS A "STRUCTURAL ENGINEER" AND NOT TAKING
 RESPONSIBILITY FOR THE MECHANICAL DESIGN.
  