2011-05-31 11:20:08****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SPANS ARE NOT CORRECT. FOR INSTANCE, IF OPENING #1
 IS 108X48, WITH A 3" EDGE DISTANCE, SPAN SHOULD EQUAL
 BLADE LENGTH FOR ACCORDION SHUTTERS (ANCHOR TO ANCHOR
 FOR PANELS).
  
 2. SPANS NOT CLEAR, PRODUCT APPROVAL IS FOR ACCORDION
 SHUTTERS BUT INSTALLATION SCHEDULE STATES THE SHUTTERS
 WILL BE INSTALLED HORIZONTALLY. ACCORDION SHUTTERS ARE
 INSTALLED VERTICALLY. REVISE INSTALLATION SCHEDULE TO
 REFLECT JOB CONDITIONS SO CODE COMPLIANCE CAN BE
 DETERMINED. FBC R 301.
  
 3. REVISE INSTALLATION SHEDULE SO THE "SHUTTER
 CONNECTION MOUNTING TYPE" CLEARLY SHOWS CONSTRUCTION
 PROPOSED. FBC R301.
  
 FOR INSTANCE, OPENING #1 (AND OTHERS) STATE THAT "4" IS
 TO BE USED. SEE SHEET 7 OF THE PRODUCT APPROVAL. IN THE
 CONCRETE BLOCK SECTION, THE SECOND COLUMN IS FOR 1&2
 WITH 4. THE THIRD COLUMN IS 3&4 W/2+5. 9" SPACING
 PROPOSED. FOR 1&2 W/4, TAPCON NOT ALLOWED AS A FASTENER
 FOR 50PSF. 3&4 REQUIRES 7.5" SPACING. PLEASE REVISE
 INSTALLATION SCHEDULE TO COMPLLY WITH REQUIREMENTS OF
 PRODUCT APPROVAL. FBC R 301.
  
 ONE TIME ONLY - DUE TO THE LENGHT OF TIME FOR REVIEW,
 CONTRACTOR MAY RESUBMIT VIA EMAIL OR FAX.
  
  
  