2011-05-04 09:17:07 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- ENGINEER TO PROVIDE THE CALCULATED RAS 117 |
| CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON |
| LAST PAGE OF NOA 10-1230.02 SUBMITTED. |
| |
| 2- FASTENER SPACING CAN'T BE LESS THAN 4"O.C. SEE SEC. |
| 8.1 OF RAS 117 CALCULATIONS. ENGINEER SPECIFIED 3"O.C. |
| FASTENER SPACING ON SECTION D FORM AND THE FLAT ROOF |
| INFORMATION FORM SUBMITTED. REVISE AS REQUIRED. PLEASE |
| DON'T USE THE PALM BEACH COUNTY FORMS. THOSE FORMS ARE |
| NO PART OF THE CITY REQUIREMENTS FOR ROOFING PERMITS. |
| PROVIDE REQUIRED INFORMATION ON SEPARATE SHEETS SIGNED |
| AND SEALED BY THE ENGINEER AS REQUIRED BY CHAPTER 471 |
| FLORIDA STATUTE. |
| |
| 3- FASTENER SPACING SHALL BE ROUNDED DOWN TO THE NEXT |
| WHOLE NUMBER NOT ROUNDED UP. SEE SEC. 10.4.5 OF RAS |
| 117. IT LOOKS LIKE ENGINEER ROUNDED UP THE FASTENER |
| SPACING FOR CORNER AREAS TO HAVE 2 ROWS IN THE CENTER |
| OF THE SHEET. SEE SECTION D AND FLAT ROOF INFORMATION |
| FORM SUBMITTED. REVISE AS REQUIRED. PLEASE DON'T USE |
| PALM BEACH COUNTY FORMS. |
| |
| 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR THE POLYFOAM TO BE USED. NONE WAS |
| SUBMITTED AT THIS TIME. PLEASE VISIT THE MIAMI-DADE |
| WEBSITE TO DOWNLOAD CURRENT NOA. |
| |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |