Plan Review Notes For Permit 11040649 |
Permit Number |
11040649 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-04-27 10:18:41 | PROVISO: | | ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED. | | NEC 210.12 | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | | |
|