2011-04-25 09:11:07 
 ELECTRICAL PLAN INSUFFICIENTLY DETAILED TO APPROVE.
 PLEASE PROVIDE THE FOLLOWING.
  
 SHOW SIZE OF THE NEW ELECTRICAL PANEL. PROVIDE A PANEL
 SCHEDULE SHOWING NEW AND EXISTING LOADS. NEC 215.5
 PROVIDE GFCI PROTECTED OUTLETS IN THE BATHROOMS. NEC
 210.52
 ALL GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12
 SHOW KITCHEN CIRCUITS WITH GFCI PROTECTION. COUNTER TOP
 RIGHT OF STOVE REQUIRES A RECEPTACLE. NEC 210.8, 210.52
 INTERCONNECT THE SD?S. FBC R313
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 A GFCI PROTECTED RECEPTACLE IS REQUIRED ON THE BALCONY.
 NEC 210.52
  
  