Plan Review Notes For Permit 11040504 |
Permit Number |
11040504 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-05-05 17:27:55 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE CLARIFY SUBSTRATE. CONNECTION TYPE A IS | | PROPOSED FOR TOP, WHICH REQUIRES A CONCRETE SUBSTRATE, | | SEE SHEET 13 OF PRODUCT APPROVAL EVALUATION REPORT. | | "CONC BLOCK" IS SPECIFIED ON THE INSTALLATION SCHEDULE; | | DOES THIS MEAN CONCRETE ON TOP AND BLOCK ON THE BOTTOM, | | OR CONCRETE BLOCK ON TOP AND BOTTOM? | | | | 2ND REVIEW, CONTRACTOR REVISED SUBSTRATE TO CONCRETE | | BLOCK TOP AND BOTTOM. SEE PRODUCT APPROVAL, SHEET 13, | | CONNECTION TYPE A REQUIRES A CONCRETE SUBSTRATE. PLEASE | | REVISE EITHER CONNECTION TYPE OR SUBSTRATE. | | | | 2. SEE CHART ON SHEET 13. 10" ANCHOR SPACING FOR | | CONNECTION TYPE D PROPOSED DOES NOT COMPLY WITH THE | | PRODUCT APPROVAL. | | | | TOP ANCHOR SPACING WILL BE REVIEWED AFTER ISSUE #1 IS | | RESOLVED. | | |
|