2011-05-05 17:27:55****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
  
 1. PLEASE CLARIFY SUBSTRATE. CONNECTION TYPE A IS
 PROPOSED FOR TOP, WHICH REQUIRES A CONCRETE SUBSTRATE,
 SEE SHEET 13 OF PRODUCT APPROVAL EVALUATION REPORT.
 "CONC BLOCK" IS SPECIFIED ON THE INSTALLATION SCHEDULE;
 DOES THIS MEAN CONCRETE ON TOP AND BLOCK ON THE BOTTOM,
 OR CONCRETE BLOCK ON TOP AND BOTTOM?
  
 2ND REVIEW, CONTRACTOR REVISED SUBSTRATE TO CONCRETE
 BLOCK TOP AND BOTTOM. SEE PRODUCT APPROVAL, SHEET 13,
 CONNECTION TYPE A REQUIRES A CONCRETE SUBSTRATE. PLEASE
 REVISE EITHER CONNECTION TYPE OR SUBSTRATE.
  
 2. SEE CHART ON SHEET 13. 10" ANCHOR SPACING FOR
 CONNECTION TYPE D PROPOSED DOES NOT COMPLY WITH THE
 PRODUCT APPROVAL.
  
 TOP ANCHOR SPACING WILL BE REVIEWED AFTER ISSUE #1 IS
 RESOLVED.
  