Plan Review Notes
Plan Review Notes For Permit 11040504
Permit Number 11040504
Review Stop B
Sequence Number 1
Notes
Date Text
2011-04-27 10:33:40****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE CLARIFY SUBSTRATE. CONNECTION TYPE A IS
 PROPOSED FOR TOP, WHICH REQUIRES A CONCRETE SUBSTRATE,
 SEE SHEET 13 OF PRODUCT APPROVAL EVALUATION REPORT.
 "CONC BLOCK" IS SPECIFIED ON THE INSTALLATION SCHEDULE;
 DOES THIS MEAN CONCRETE ON TOP AND BLOCK ON THE BOTTOM,
 OR CONCRETE BLOCK ON TOP AND BOTTOM?
  
 2. NO ANCHOR SPACING SPECIFIED. PLEASE COMPLETE THE
 INSTALLATION SCHEDULE.
  
  