2011-05-05 17:00:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. ALTHOUGH THE INSTALLATION SCHEDULE SUBMITTED IN THE
 FIRST REVIEW WAS NOT CODE COMPLIANT, A REVISED
 INSTALLATION SCHEDULE WAS NOT RESUBMITTED. PLEASE
 COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. A RESPONSE NOTE WAS INCLUDED IN THE RESUBMITTAL
 WHICH STATED: "TPS=13" ACC=7.4" ANCHOR SPACING"
  
 PLEASE SEE THE ACCORDION PRODUCT APPROVAL, SHEET 10.
 THE SUBSTRATE FOR THE TOP CAN BE CONCRETE, BUT THE
 BOTTOM IS USUALLY CONCRETE BLOCK (MASONRY). THE
 CONNECTION TYPE CIRCLED ON THE CONCRETE SUBSTRATE
 ANCHOR CHART, C4, IS NOT PERMITTED FOR HOLLOW BLOCK
 SUBSTRATE, TAPCON ANCHOR. OTHER ANCHORS ARE PERMITTED
 PER SHEET 10 OF THE PRODUCT APPROVAL. INSTALLATION
 METHOD PROPOSED DOES NOT COMPLY. PLEASE REVISE THE
 INSTALLATION SCHEDULE AND RESUBMIT.
  
  
  