2011-04-21 11:06:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE EXPOSURE CATEGORY (TO EXPOSURE C) OR PROVIDE
 ENGINEERING FOR EXPOSURE B PRESSURES. FBC1609, FBC
 R301.2.1.4. NOTE THAT THE CODE CHANGED EFFECTIVE MARCH
 1, 2009.
  
 2. THE ANCHOR CHARTS ON THE PRODUCT APPROVAL HAVE
 SPACING CIRCLED ON THE CONCRETE SUBSTRATE CHART. PRIOR
 TO RESUBMITTAL, PLEASE CONFIRM THAT ANCHOR SPACING
 COMPLIES WITH REQUIREMENTS FOR CONCRETE BLOCK SUBSTRATE
 AND INCREASED DESIGN PRESSURES. IT APPEARS THAT
 INCORRECT ANCHOR SPACING HAS BEEN SPECIFIED ON THE
 INSTALLATION SCHEDULE.
  
  
  
  