2011-04-19 11:01:06PROVIDE AN ELECTRIC PLAN. LOCATE EXISTING SERVICE, MAIN
 DISCONNECTS AND PANELS ON THE FLOOR PLAN. PROVIDE AN
 ELECTRICAL RISER DIAGRAM FOR THE NEW SERVICE. NEC
 110.26
 RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11
 ALL NEW RECEPTACLES WITHIN THE DWELLING SHALL BE
 PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER.
 NEC 210-12 (B)
 SUMMARIZE THE ELECTRICAL LOAD TO VERIFY THE NEW
 CAPACITY IS SUFFICIENT. NEC 220
  
 REMODELING OF AN EXISTING STRUCTURE SHALL INCLUDE
 INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT ALREADY
 EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. FBC R313
  