Plan Review Notes For Permit 11040378 |
Permit Number |
11040378 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-04-19 11:01:06 | PROVIDE AN ELECTRIC PLAN. LOCATE EXISTING SERVICE, MAIN | | DISCONNECTS AND PANELS ON THE FLOOR PLAN. PROVIDE AN | | ELECTRICAL RISER DIAGRAM FOR THE NEW SERVICE. NEC | | 110.26 | | RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11 | | ALL NEW RECEPTACLES WITHIN THE DWELLING SHALL BE | | PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER. | | NEC 210-12 (B) | | SUMMARIZE THE ELECTRICAL LOAD TO VERIFY THE NEW | | CAPACITY IS SUFFICIENT. NEC 220 | | | | REMODELING OF AN EXISTING STRUCTURE SHALL INCLUDE | | INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT ALREADY | | EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. FBC R313 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|