2011-04-18 10:28:51*****PROVISO******
  
 1.SEPARATE MED GAS APPLICATION, PERMIT, AND FEES
 REQUIRED
  
 2. 713.7 CENTRAL VACUUM OR DISPOSAL SYSTEMS. WHERE THE
 WASTE FROM A CENTRAL VACUUM (FLUID SUCTION) SYSTEM OF
 THE BAROMETRIC-LAG, COLLECTION-TANK OR BOTTLE-DISPOSAL
 TYPE IS CONNECTED TO THE DRAINAGE SYSTEM, THE WASTE
 SHALL BE DIRECTLY CONNECTED TO THE SANITARY DRAINAGE
 SYSTEM THROUGH A TRAPPED WASTE.
  
 3. 301.12 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 ROOF MOUNTED MECHANICAL UNITS AND SUPPORTS SHALL BE
 SECURED TO THE STRUCTURE. THE USE OF WOOD "SLEEPERS"
 SHALL NOT BE PERMITTED.
  
 4.307.2.1 CONDENSATE DISPOSAL. CONDENSATE FROM ALL
 COOLING COILS AND EVAPORATORS SHALL BE CONVEYED FROM
 THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF DISPOSAL.
 CONDENSATE SHALL NOT DISCHARGE INTO A STREET, ALLEY OR
 OTHER AREAS SO AS TO CAUSE A NUISANCE.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR