Plan Review Notes For Permit 11040299 |
Permit Number |
11040299 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-04-18 10:28:51 | *****PROVISO****** | | | | 1.SEPARATE MED GAS APPLICATION, PERMIT, AND FEES | | REQUIRED | | | | 2. 713.7 CENTRAL VACUUM OR DISPOSAL SYSTEMS. WHERE THE | | WASTE FROM A CENTRAL VACUUM (FLUID SUCTION) SYSTEM OF | | THE BAROMETRIC-LAG, COLLECTION-TANK OR BOTTLE-DISPOSAL | | TYPE IS CONNECTED TO THE DRAINAGE SYSTEM, THE WASTE | | SHALL BE DIRECTLY CONNECTED TO THE SANITARY DRAINAGE | | SYSTEM THROUGH A TRAPPED WASTE. | | | | 3. 301.12 WIND RESISTANCE. MECHANICAL EQUIPMENT, | | APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL | | BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES | | ON THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN | | ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. | | ROOF MOUNTED MECHANICAL UNITS AND SUPPORTS SHALL BE | | SECURED TO THE STRUCTURE. THE USE OF WOOD "SLEEPERS" | | SHALL NOT BE PERMITTED. | | | | 4.307.2.1 CONDENSATE DISPOSAL. CONDENSATE FROM ALL | | COOLING COILS AND EVAPORATORS SHALL BE CONVEYED FROM | | THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF DISPOSAL. | | CONDENSATE SHALL NOT DISCHARGE INTO A STREET, ALLEY OR | | OTHER AREAS SO AS TO CAUSE A NUISANCE. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | | | | | |
|