2011-04-21 10:35:03 | 2431 SOUTH DIXIE HIGHWAY | | PERMIT #11040299 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | COVER SHEET POST NUMERICAL ADDRESS ON THE BUILDING. | | NUMBERS SHALL BE AT LEAST SIX INCHES IN HEIGHT AND | | SHALL CONTRAST THE BACKGROUND PER SECTION 10.12.1.2 OF | | NFPA 1 FLORIDA EDITION. | | | | SHEET A100 A CURB OR BARRIER SHALL BE PROVIDED THAT | | PREVENTS THE PASSAGE OF A 4 INCH DIAMETER SPHERE WHERE | | ANY PORTION OF THE SPHERE IS WITHIN 4 INCHES OF THE | | FLOOR OR GROUND SURFACE PER SECTION 7.2.5.4.1.2 OF NFPA | | 101 FLORIDA EDITION. | | | | SHEET A101 DEMOLITION WORK SHALL COMPLY WITH NFPA 241. | | | | SHEET A102 | | PROVIDE LIFE SAFETY PLAN INDICATING TRAVEL DISTANCES, | | FIRE EXTINGUISHERS ETC. EXTINGUISHERS SHALL HAVE A | | MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY A | | LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO | | EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | PER SECTION 38.3.2.1 (FFPC) THE STORAGE ROOM IS | | REQUIRED TO BE PROTECTED WITH A ONE HOUR FIRE RATED | | BARRIER WITHOUT WINDOWS OR AN AUTOMATIC SPRINKLER | | SYSTEM. DOORS WILL BE REQUIRED TO BE FIRE RATED AND | | SELF CLOSING. | | | | INDICATE WHAT TYPE OF MATERIALS, MEDICAL GAS CYLINDERS, | | ETC. WILL BE STORED IN THE STORAGE ROOM. | | | | PROVIDE STAIR DETAILS. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|