Plan Review Notes
Plan Review Notes For Permit 11040299
Permit Number 11040299
Review Stop B
Sequence Number 1
Notes
Date Text
2011-04-20 12:16:09BUILDING PLAN REVIEW
 PERMIT: 11040299
 ADD: 2431 S DIXIE HWY
 CONT: TBD
 TEL: (954)557-1300
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A102:
 1A) DOOR # 4 VERSES THE DRINKING FOUNTAIN. THE OUT
 SWING OF DOOR # 4 DOES NOT HAVE THE REQUIRED 18 INCHES
 ON THE LATCH SIDE. PLEASE REVIEW 11-4.13.6.
  
 1B) THE SECOND ISSUE WITH DOORWAYS BOTH DOORWAYS 5 &6
 ARE ILLUSTRATERD AS A PAIR OF DOUBLE DOORS. THE DOOR
 SCHEDULEFOR DOOR # 5 INDICATES A 3'-0" DOOR NOT A PAIR
 OF DOORS.
  
 1C) THE DOOR SCHEDULE ALSO DOESN'T INDICATE TYPE OF
 HARDWARE, PLEASE INDICATE COMPLIANCE WITH 11-4.13.4.
  
 1D) DOOR # 5 VERSES THE DRINKING FOUNTAIN MAY BECOME
 MORE OF AN ISSUE IF IT IS MOVED DOWN TTHE WALL TO
 COMPLY WITH DOOR # 4.
  
 2) DOOR # 1 & 17, WILL BE RAISED APPROXIMATELY ONE FOOT
 WITH THE NEW FLOOR LEVEL. I DIDN'T SEE ANY CUT SECTIONS
 THROUGH THE PLANS INDICATING HOW THE NEW ELEVATIONS ARE
 GOING TO EFFECT THE EXISTING LINTELS AND OR BEAM. SHEET
 S-3 DETAIL # 1 DOES HAVE A NOTE TO VEREIFY EXISTING
 BEAM CONDITION.
  
 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3A) WINDOWS FIXED GLASS
 3B) EXTERIO DOORS
 3C)ROOFING APPROVALS BOTH FLAT AND TILE
 3D) ROOF TOP EXHAUST FANS
  
 PLANS SUBMITTED ARE TO BE DETERMINED, SINCE THE
 PRESSURES ON THE BUILDING ARE CORRECT THIS PERMIT CAN
 BE ISSUED WITH THE PRODUCT APPROVALS COMING IN AT A
 LATER DATE AFTER ISSUANCE. NOTE IN DOING SO THIS WILL
 CONSTITUTE A REVISION REQUIRING SEPERATE REVIEWS AND
 ASSOCIATED FEES!!! FOR EACH PRODUCT APPROVAL TO BE
 SUBMITTED. PLEASE NOTE IN MANY CASES THERE ARE WITHIN
 THE PRODUCT APPROVAL THERE ARE EITHER SUB-SYSTEMS OR
 DIFFERENT TYPES OF GLAZING WITH DIFFERENT PRESSURES,
 PLEASE CIRCLE WHICH SYSTEM TO BE INSTALLED UNDER THIS
 PERMIT.
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) AT THE REAR OF THE BUILDING THERE IS A DOWN SPOUT
 NEAR DOOR # 17, THIS DOWN SPOUT IS ALSO LOCATED ON A105
 PLEASE PROVIDE WHERE THIS DOWN SPOUT IS GOING TO DRAIN.
 2007 FBC-B 1503.6.
  
 6) SHEET A104 THE PLANS HAVE A STATEMENT THAT THE
 ROOFING INSULATION SHALL BE RIGID INSULATION A AVERAGE
 R-20.
 INFORMAL BOAF INTERPRETATION
 DATE: TUE NOV 13 2007
 REPORT #: 5438
 CODE: BUILDING
 SECTION: 404.1.A
 QUESTION:
 IS IT THE INTENT OF THE CODE "....THE INSULATION SHALL
 HAVE A R-VALUE OF AT LEAST R-19, SPACE PERMITTING." TO
 MEAN THE MINIMUM R-VALUE OF ROOF INSULATION TO BE R-19
 AT LOWEST POINTS AT DRAINS? ALL ROOFERS WHO WE HAVE
 SPOKEN TO, INTERPRETED THIS CODE AS MINIMUM AVERAGE
 R-19,
 NOT MINIMUM R-19 AND HAVE DONE MOST ROOFING JOB
 ACCORDINGLY. THANK YOU
 ANSWER:
 A MINIMUM LEVEL OF INSULATION REQUIRED IS THAT, A
 MINIMUM, NOT AN AVERAGE. HOWEVER, PROVIDED THE MINIMUM
 R-19 VALUE HAS BEEN MET, A REASONABLE AVERAGING
 PROCEDURE CAN BE USED BY ROOF AREA FOR CALCULATIONS OF
 THE VALUE.
 COMMENTARY:
 THIS QUESTION ACTUALLY REFERS TO SECTION 13-404.1 (A)
 PRESCRIPTIVE REQUIREMENTS SPECIFIC TO METHOD A. THIS
 SECTION MANDATES COMPLIANCE WITH FLA/COM METHOD A,
 HOWEVER GIVES A PRESCRIPTIVE REQUIREMENT OF AN R-19 FOR
 MULTIFAMILY RESIDENTIAL ROOF/CEILING ASSEMBLY. AS SPACE
 PERMITS, MAY RELATE TO THE AREA OF THE EAVES WHERE THE
 R- 19 INSULATION WOULD HAVE TO BE COMPRESSED TO FIT IN
 THE SPACE AVAILABLE. HOWEVER, THE PETITIONER ALLUDES TO
 THE ROOFER INSTALLING THE INSULATION. THERE ARE NO
 SPACE CONSTRAINTS FOR INSULATION APPLIED TO A ROOF
 DECK; IT SHOULD BE R-19 MINIMUM. IF THE BUILT-UP ROOF
 IS SLOPING TO A DRAIN IN A MANNER WHERE SOME PARTS OF
 THE ROOF HAVE MORE THAN R-19 AND SOME HAVE LESS, THEN
 THE RESIDENT WHOSE APARTMENT/CONDO IS UNDER THE ROOF
 SECTION WITH LESS THAN R- 19 WOULD BE PENALIZED WITH
 HIGHER HEAT LOADS AND HIGHER ENERGY COSTS THAN THEIR
 NEIGHBOR.
  
 7) SHEET A104 & A104A BOTH INDICATE NEW ROOF TOP A/C
 CURBS BUT THE PLANS DO NOT INDICATE HOW THEY ARE TO BE
 ATTACHED TO THE ROOF FRAMING (BAR JOIST SYSTEM? NO
 INFORMATION IS PROVIDED FOR THIS DETAIL IN TTHE
 STRUCTURAL PLANS EITHER.
  
 8) PLANS ARE NOT CLEAR AS TO THE EXTERIOR WALLS AND
 TYPE OF INSULATION TO BE USED AND WHAT POINT THE
 INSULATION WILL END IN RELATION TO THE ROOFING
 ASSEMBLY? FBC-B 2603.4 & FBC-M 602.1.5.1.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved