2011-04-19 15:42:57 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| 1. INSTALLATION SCHEDULE, SHUTTER CONNECTION MOUNTING |
| TYPES A AND I REQUIRE POURED CONCRETE SUBSTRATE. PLEASE |
| NOTE THAT MOST CBS STRUCTURES HAVE A POURED CONCRETE |
| TOP CONNECTION SUBSTRATE, CONCRETE BLOCK AT BOTTOM. |
| |
| 2. A 2 1/2" EDGE DISTANCE REQUIRES A .35 FACTOR, SEE |
| CHART ON SHEET 14. THIS HAS NOT BEEN APPLIED TO THE |
| ANCHOR SPACING. |
| |
| 3. WALL PRESURES PROPOSED ON THE INSTALLATION SCHEDULE |
| ARE +47/-62 PSF. IT APPEARS THAT CONTRACTOR USED THE |
| COLUMN FOR -60PSF, BUT -62 PSF IS A GREATER PRESSURE |
| THAN -60PSF. THE NEXT COLUMN MUST BE USED, -75PSF. |
| |
| 4. CONNECTION TYPE L HAS BEEN CIRCLED ON SHEET 15, BUT |
| I HAS BEEN SPECIFIED ON THE INSTALLATION SCHEDULE. THE |
| INFORMATION MARKED ON THE PRODUCT APPROVAL IS TO |
| CORRELATE WITH THE INSTALLATION SCHEDULE. |
| |
| 5. THE QUALIFIER IS TO REVIEW ALL PERMIT DOCUMENTS |
| PRIOR TO SUBMITTAL. PLEASE HAVE THE QUALIFIER REVIEW |
| THE INSTALLATION SCHEDULE AND CONTACT ME IF HE NEEDS |
| ASSISTANCE. WHEN RESUBMITTING, CONTRACTOR IS TO STATE |
| THAT HE HAS REVIEWED THE INSTALLATION SCHEDULE AND THAT |
| IT COMPLIES WITH THE REQUIREMENTS OF THE PRODUCT |
| APPROVAL AND FBC. |
| |
| 6. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. |
| INCLUDE ROOM DESIGNATION AND OPENING TYPE. |
| |