Plan Review Notes For Permit 11040253 |
Permit Number |
11040253 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-06-15 17:06:20 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) SPECIFY THE FILE NUMBER OR DESIGN NUMBER OF THE ONE | | HOUR FIRE-RATED SEPARATION WALL BETWEEN THE TWO UNITS. | | ANSI/UL 263 IS THE TEST METHOD AND ACCEPTANCE CRITERIA. | | | | 2) THE ENERGY CALCULATIONS ARE INCORRECT. THE NUMBER OF | | WINDOWS AND DOORS IN EACH UNIT ARE INCORRECT. THE PLANS | | SHOW A GABLE ROOF NOT A HIP. THIS COMMENT WAS UNDER | | MECHANICAL REVIEW IN THE FIRST REVIEW. THE FORM DOES | | NOT SPECIFY TWO UNITS. THE COMMON WALL BETWEEN THE TWO | | UNITS IS NOT LISTED ON THE FORM. THERE ARE ONLY TWO | | DOORS AND THE FORM LISTS THREE. THE FORM ONLY LISTS 8 | | WINDOWS AND THE ELEVATION PLANS SHOW 14. PLEASE | | CORRECT. | | | | 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR | | NON-IMPACT RATED WINDOWS. IMPACT PROTECTION IS REQUIRED | | BY FBC R301.2.1.2 AND FBC EXISTING BUILDING 606.4. | | UNLESS THERE ARE EXISTING STORM PANELS, SUBMIT TWO | | COPIES OF PRODUCT APPROVALS AND AN INSTALLATION | | SCHEDULE FOR THE STORM PANELS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|