Plan Review Notes For Permit 11040253
Permit Number 11040253
Review Stop B
Sequence Number 2
Notes
Date Text
2011-06-15 17:06:202007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SPECIFY THE FILE NUMBER OR DESIGN NUMBER OF THE ONE
 HOUR FIRE-RATED SEPARATION WALL BETWEEN THE TWO UNITS.
 ANSI/UL 263 IS THE TEST METHOD AND ACCEPTANCE CRITERIA.
  
 2) THE ENERGY CALCULATIONS ARE INCORRECT. THE NUMBER OF
 WINDOWS AND DOORS IN EACH UNIT ARE INCORRECT. THE PLANS
 SHOW A GABLE ROOF NOT A HIP. THIS COMMENT WAS UNDER
 MECHANICAL REVIEW IN THE FIRST REVIEW. THE FORM DOES
 NOT SPECIFY TWO UNITS. THE COMMON WALL BETWEEN THE TWO
 UNITS IS NOT LISTED ON THE FORM. THERE ARE ONLY TWO
 DOORS AND THE FORM LISTS THREE. THE FORM ONLY LISTS 8
 WINDOWS AND THE ELEVATION PLANS SHOW 14. PLEASE
 CORRECT.
  
 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 NON-IMPACT RATED WINDOWS. IMPACT PROTECTION IS REQUIRED
 BY FBC R301.2.1.2 AND FBC EXISTING BUILDING 606.4.
 UNLESS THERE ARE EXISTING STORM PANELS, SUBMIT TWO
 COPIES OF PRODUCT APPROVALS AND AN INSTALLATION
 SCHEDULE FOR THE STORM PANELS.
  