2011-05-13 15:33:482007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE SPECIFY THE DUCT SIZES, GRILL SIZES AND CFMS FOR
 EACH DROP FOR THE A/C SUPPLIES FOR UNIT B. CITY
 AMENDMENTS 106.3.5.4
  
 2) THE ENERGY CALCULATIONS ARE INCORRECT. THE NUMBER OF
 WINDOWS AND DOORS IN EACH UNIT ARE INCORRECT. THE PLANS
 SHOW A GABLE ROOF NOT A HIP. THE EXTERIOR WALLS ARE
 INCORRECT. THE ENERGY FORM SPECIFIES THE COOLING
 SYSTEMS AS 14 SEER AND ONE OF THE UNITS IS SPECIFIED AS
 13 SEER ON THE MECHANICAL PLAN. FBC 13-101.2.3 PLEASE
 CORRECT.
  
 3) THE EQUIPMENT SIZING CALCULATIONS DO NOT MATCH THE
 SPECIFIED EQUIPMENT. FBCR M1401.3
  
 4) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA "A-9" BFE 13'. ALL NEW EQUIPMENT SERVICING THE
 DWELLINGS WILL BE REQUIRED TO BE 6" ABOVE THE BASE
 FLOOD ELEVATION WHICH IS A MINIMUM OF 13'-6".
  