Plan Review Notes For Permit 11040253 |
Permit Number |
11040253 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-05-13 15:33:48 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) THE SPECIFY THE DUCT SIZES, GRILL SIZES AND CFMS FOR | | EACH DROP FOR THE A/C SUPPLIES FOR UNIT B. CITY | | AMENDMENTS 106.3.5.4 | | | | 2) THE ENERGY CALCULATIONS ARE INCORRECT. THE NUMBER OF | | WINDOWS AND DOORS IN EACH UNIT ARE INCORRECT. THE PLANS | | SHOW A GABLE ROOF NOT A HIP. THE EXTERIOR WALLS ARE | | INCORRECT. THE ENERGY FORM SPECIFIES THE COOLING | | SYSTEMS AS 14 SEER AND ONE OF THE UNITS IS SPECIFIED AS | | 13 SEER ON THE MECHANICAL PLAN. FBC 13-101.2.3 PLEASE | | CORRECT. | | | | 3) THE EQUIPMENT SIZING CALCULATIONS DO NOT MATCH THE | | SPECIFIED EQUIPMENT. FBCR M1401.3 | | | | 4) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA "A-9" BFE 13'. ALL NEW EQUIPMENT SERVICING THE | | DWELLINGS WILL BE REQUIRED TO BE 6" ABOVE THE BASE | | FLOOD ELEVATION WHICH IS A MINIMUM OF 13'-6". | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|