2011-04-19 14:23:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. VALUE IS TO INCLUDE LABOR AND MATERIALS. PROVIDE AN
 INVOICE FROM STORM DEPOT TO PROVIDE EVIDENCE OF
 MATERIAL COST.
  
 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.
  
 3. PROVIDE INFORMATION TO SHOW HOW YOU HAVE DETERMINED
 THAT THE SUBSTRATE ON THE BOTTOM IS CONCRETE. TYPICALLY
 THE SUBSTRATE IS CONCRETE AT THE TOP, CONCRETE AT THE
 BOTTOM. ALTERNATIVELY, REVISE BOTTOM SUBSTRATE TO
 CONCRETE BLOCK AND REVISE ANCHOR SPACING ACCORDINGLY.
 FBC R301.
  
 4. PROVIDE INFORMATION REGARDING THE EMERGENCY MEANS OF
 ESCAPE, FBC R310.4. SHOW ROOM DESIGNATIONS AND TYPE OF
 OPENING. TWO OPENINGS ARE SHOWN ON THE FLOOR PLAN AS
 "EXIT" BUT BOTH ARE TO BE COVERED WITH ACCORDION
 SHUTTERS. IT IS NOT CLEAR HOW THE OPENINGS WILL COMPLY
 WITH THE REQUIREMENTS OF THE CODE.
  
 5. THE "SHUTTER CONNECTION MOUNTING TYPE" ON THE
 INSTALLATION SCHEDULE IS TO CORRELATE WITH THE ANCHOR
 CHART, SEE PAGE 6. BASED ON INFORMATION HIGHLIGHTED, IT
 APPEARS THAT YOU PROPOSE TO USE MOUNTING TYPE "C2," SEE
 PAGE 3 OF PRODUCT APPROVAL. PLEASE NOTE THAT
 HIGHLIGHTED INFORMATION DOES NOT APPEAR WHEN SCANNED,
 AND CANNOT BE USED TO SHOW CODE COMPLIANCE. PLEASE
 REVISE THE INSTALLATION SCHEDULE TO INCLUDE REQUIRED
 INFORMATION.
  
 6. SHUTTER SPAN FOR AN ACCORDION SHUTTER IS THE BLADE
 LENGTH. SEE OPENING 6, 268" IS STATED AS SPAN. THIS
 EXCEEDS THE MAXIMUM PERMITTED BY THIS PRODUCT APPROVAL;
 HOWEVER, IT APPEARS THAT YOU HAVE USED THE SHUTTER
 WIDTH. PLEASE ADDRESS.
  
  
  