Plan Review Notes
Plan Review Notes For Permit 11040166
Permit Number 11040166
Review Stop M
Sequence Number 1
Notes
Date Text
2011-05-16 15:57:392009 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE TITLE BLOCK HAS THE NAME AND LICENSE NUMBER OF
 THE ARCHITECT, THEREFORE THE MECHANICAL PLANS ARE
 REQUIRED TO BE SIGNED AND SEALED BY HIM PER FLORIDA
 STATUTES 481. IF THERE IS NO ACHITECT OR ENGINEERS
 TITLE BLOCK, SYSTEMS LESS THAN 15-TONS AND DESIGNED TO
 ACCOMMODATE 100 OR FEWER PERSONS CAN BE DESIGNED BY AN
 A/C OR MECHANICAL CONTRACTOR PER FS471.003(H). THE
 NAME, SIGNATURE AND LICENSE NUMBER OF THE CONTRACTOR IS
 REQUIRED ON THE PLANS.
  
 2) THE ENERGY CALCULATIONS CONTAINS THE FOLLOWING
 ERRORS: 1) THE ENERGY CALC. FORM SPECIFIES A VENTED
 ATTIC WITH R-30 INSULATION AND THE PLAN SHEET A11
 SPECIFIES ICYNENE SPRAY FOAM INSULATION IN A NON-VENTED
 ATTIC. 2) THE PLANS SPECIFY CLAY TILE AND NOT
 COMPOSITION SHINGLES. 3) THE (2) WATER HEATERS ARE GAS
 AND NOT ELECTRIC. PLEASE REVIEW AND CORRECT THE ENERGY
 CALCULATIONS. SEE FBC 13-101.2
  
 3) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER/AGENT. FBC 13-103.1.2
  