Date |
Text |
2011-05-19 10:36:23 | 2007 FBC W/2009 REVISIONS |
| |
| DENIED BY BUILDING |
| |
| 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A |
| MINIMUM ELEVATION REQUIREMENT OF 7'-6" PER THE CITY OF |
| WEST PALM BEACH CITY FLOOD PLAIN ORDINANCE ARTICLE |
| XVII. THE GARAGE FLOOR ELEVATION IS REQUIRED TO BE A |
| MINIMUM OF 7'-6" OR BE CONSTRUCTED WITH FLOOD DAMAGE |
| RESISTANT MATERIALS AND FLOOD VENTS. FBC R323 |
| |
| 2) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED |
| AND DATED BY THE OWNER/AGENT. THERE ARE ALSO MISTAKES |
| IN THE CALCULATIONS. SEE MECHANICAL REVIEW COMMENTS. |
| FBC 13-103 |
| |
| 3) SUBMIT TWO COPIES OF THE SPECIFICATIONS FOR THE |
| ICYNENE SPRAY FOAM INSULATION AND SPECIFY THE IGNITION |
| BARRIER THAT WILL BE USED. FBC R314 |
| |
| 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| THE PROJECT PER CITY AMENDMENTS 106.3.3. |
| |
| 5) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| TO INSTALL THE CLAY ROOF TILE AND SUBMIT THE PRODUCT |
| APPROVALS FOR IT. DCA RULE 9B-72 |
| |
| 6) SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR ENHANCED FASTENING OF THE BASE SHEET |
| FOR THE GAF MODIFIED ROOFING MATERIAL AS REQUIRED BY |
| LIMITATION # 7 OF THE PRODUCT APPROVAL. |
| |
| 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| OUT-SWING SERVICE DOOR AT THE GARAGE AS REQUIRED BY DCA |
| RULE 9B-72. |
| |
| 8) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| SERIES "450" ALUMINUM DOOR HAS BEEN SUPERSEDED. PLEASE |
| SUBMIT THE CURRENT NOA NO. 09-0723.04. |
| |
| 9) THE TRUSS DRAWINGS AND LAYOUT ARE REQUIRED TO BE |
| REVIEWED BY THE DESIGNER OF RECORD FOR THE STRUCTURE. |
| THE D.O.R. SHOULD STAMP THE LAYOUT WITH A SHOP DRAWING |
| REVIEW STAMP. NOTE: THE TRUSS DRAWINGS AND LAYOUT FOR |
| SINGLE FAMILY HOMES CAN BE GIVEN TO THE FIELD INSPECTOR |
| AT THE TRUSS INSPECTION. |
| |
| 10) PROVIDE ROOF DRAIN AND OVERFLOW SCUPPER SIZING |
| CALCULATIONS FOR THE BALCONY AS REQUIRED BY FBC R903.4 |
| AND FBC 1106 & 1107. |
| |
| 11) TWO SETS OF SHOP DRAWINGS APPROVED BY THE DESIGNER |
| OF RECORD FOR THE STRUCTURE FOR THE PRECAST HOLLOW CORE |
| SLAB SYSTEM WILL BE REQUIRED TO BE SUBMITTED PRIOR TO |
| INSTALLATION. |
| |
| 12) SUBMIT TWO SETS OF SPECIFICATIONS AND INSTALLATION |
| INSTRUCTIONS FOR THE BUILT-IN BBQ ON THE COVERED PORCH. |
| FBCR M1306.1 |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |