Plan Review Notes
Plan Review Notes For Permit 11040073
Permit Number 11040073
Review Stop B
Sequence Number 1
Notes
Date Text
2011-04-04 14:13:49RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE
 OF NOA 08-0410.09 SUBMITTED.
 ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO
 TAKE INTO CONSIDERATION THAT THIS BUILDING IS LOCATED
 ON EXPOSURE "C". SEC. R301.2.1.4.3.
  
 2- A) SPECIFY HOW IS THE ROOF TILE GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.
  
 B) IF USING POLYFOAM, THEN PROVIDE 2 COPIES OF PRODUCT
 APPROVALS AS REQUIRED BY DCA RULE 9B-72.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712