Plan Review Notes For Permit 11040048 |
Permit Number |
11040048 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-04-04 09:45:06 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- FLAT ROOF NOA 07-1203.01 SUBMITTED WAS SUPERSEDED BY | | MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. VISIT | | MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. | | | | 2- SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE | | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | PRESSURES OF SEC. R301. | | | | 3- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|