2011-04-01 10:41:41 | THE ENTRANCE DOOR TO THE SWITCHGEAR NEEDS TO SWING IN | | THE DIRECTION OF EGRESS AND BE EQUIPPED WITH PANIC | | BARS. NEC 110.26 (C)(3). | | | | PLEASE PROVIDE ADDITIONAL INFORMATION ON THE EXISTING | | FEEDER SIZE FOR FLOORS 1, 2, AND 3. INDICATE THE OC | | PROTECTION PROPOSED FOR PP3 AND PP2. OC PROTECTION FOR | | THE EXISTING #250 KCMIL ( 255 AMPS) FEEDERS SHOULD BE | | LIMITED TO 300 AMPS. NEC 240.6, T 310.16 | | | | ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718 | | | | |
|