Plan Review Notes
Plan Review Notes For Permit 11030690
Permit Number 11030690
Review Stop E
Sequence Number 1
Notes
Date Text
2011-04-01 10:41:41THE ENTRANCE DOOR TO THE SWITCHGEAR NEEDS TO SWING IN
 THE DIRECTION OF EGRESS AND BE EQUIPPED WITH PANIC
 BARS. NEC 110.26 (C)(3).
  
 PLEASE PROVIDE ADDITIONAL INFORMATION ON THE EXISTING
 FEEDER SIZE FOR FLOORS 1, 2, AND 3. INDICATE THE OC
 PROTECTION PROPOSED FOR PP3 AND PP2. OC PROTECTION FOR
 THE EXISTING #250 KCMIL ( 255 AMPS) FEEDERS SHOULD BE
 LIMITED TO 300 AMPS. NEC 240.6, T 310.16
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718
  
  