 REVIEW COMMENTS ? FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS*****
  
 PROVIDE FIRE ALARM NOTIFICATION APPLIANCE FOR OUTDOOR
 SEATING AREA.
  
 PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE CANOPY
 MATERIAL.
  
 STAIRS AND EGRESS COMPONENTS SHALL CONFORM TO THE LIFE
 SAFETY REQUIREMENTS OF CHAPTER 7 OF NFPA 101 FLORIDA
 2007 EDITION.
  
 STAIRS SHALL BE A MINIMUM OF 36 INCHES IN WIDTH.
  
 PROVIDE PERMANENT WEATHERPROOF EXIT SIGN ATTACHED TO
 SWINGING EGRESS GATE.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN
 HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A
 MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE
 ACCUMULATION OF WATER.
  
 STAIRS SHALL HAVE LANDINGS AT DOOR OPENINGS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  