Plan Review Notes For Permit 11030661 |
Permit Number |
11030661 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-03-25 13:30:58 | 101 CLEMATIS STREET, SUITE #100 | | PERMIT #11030661 | | MASTER #10070589 | | REVIEW COMMENTS ? FIRE DEPARTMENT | | | | *****APPROVED WITH PROVISIONS***** | | | | PROVIDE FIRE ALARM NOTIFICATION APPLIANCE FOR OUTDOOR | | SEATING AREA. | | | | PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE CANOPY | | MATERIAL. | | | | STAIRS AND EGRESS COMPONENTS SHALL CONFORM TO THE LIFE | | SAFETY REQUIREMENTS OF CHAPTER 7 OF NFPA 101 FLORIDA | | 2007 EDITION. | | | | STAIRS SHALL BE A MINIMUM OF 36 INCHES IN WIDTH. | | | | PROVIDE PERMANENT WEATHERPROOF EXIT SIGN ATTACHED TO | | SWINGING EGRESS GATE. | | | | HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR. | | HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND | | NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, | | MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE | | LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE | | RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT | | NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A | | DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN | | 2 INCHES. | | | | STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN | | HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A | | MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE | | ACCUMULATION OF WATER. | | | | STAIRS SHALL HAVE LANDINGS AT DOOR OPENINGS. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|