2011-03-24 16:39:211200 7TH STREET
 PERMIT #11030392
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: THIS IS A CHANGE OF OCCUPANCY FROM EXISTING
 FAMILY DWELLING TO NEW BUSINESS.
  
  
 EXITING SHALL COMPLY WITH LIFE SAFETY CODE CHAPTER 7 OF
 NFPA 101 FLORIDA EDITION 2007.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 PROVIDE EXIT SIGNS AND TACTILE SIGNAGE AT EXIT DOORS
 READING EXIT.
  
 COOKING EQUIPMENT SHALL BE PROTECTED WITH A FIXED FIRE
 SUPPRESSION SYSTEM.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  