2011-03-24 16:39:21 | 1200 7TH STREET |
| PERMIT #11030392 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NOTE: THIS IS A CHANGE OF OCCUPANCY FROM EXISTING |
| FAMILY DWELLING TO NEW BUSINESS. |
| |
| |
| EXITING SHALL COMPLY WITH LIFE SAFETY CODE CHAPTER 7 OF |
| NFPA 101 FLORIDA EDITION 2007. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| ADMINISTRATIVE CODE 69A-60.0081. |
| |
| PROVIDE EXIT SIGNS AND TACTILE SIGNAGE AT EXIT DOORS |
| READING EXIT. |
| |
| COOKING EQUIPMENT SHALL BE PROTECTED WITH A FIXED FIRE |
| SUPPRESSION SYSTEM. |
| |
| THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE |
| DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA |
| EDITION 2007. |
| |