2011-04-01 13:31:40 | BUILDING PLAN REVIEW |
| PERMIT: 11030392 |
| ADD: 1200 7TH ST |
| CONT: TBD |
| TEL: (561)###-#### |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| NOTE: THIS IS A CHANGE OF OCCUPANCY: |
| |
| 1) 906.1 GENERAL. ACCESSIBILITY IN PORTIONS OF |
| BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE |
| FLORIDA BUILDING CODE, BUILDING . |
| 2007 FBC-B 11-4.1.6(2) |
| DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF |
| DISPROPORTIONALITY. |
| |
| (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE |
| PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| DISPROPORTIONATE COSTS. |
| |
| (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| ORDER: |
| |
| (I) AN ACCESSIBLE ENTRANCE; |
| |
| (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA: |
| |
| (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR |
| A SINGLE UNISEX RESTROOM: |
| |
| (IV) ACCESSIBLE TELEPHONES; |
| |
| (V) ACCESSIBLE DRINKING FOUNTAINS; AND |
| |
| (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH |
| AS PARKING, STORAGE, AND ALARMS. |
| |
| 912.8 ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS |
| THEREOF THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2) 912.4.2 MEANS OF EGRESS FOR CHANGE OF USE TO EQUAL |
| OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY |
| CLASSIFICATION IS MADE TO AN EQUAL OR LESSER HAZARD |
| CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE 912.4, |
| EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL COMPLY |
| WITH THE REQUIREMENTS OF SECTION 805 FOR THE NEW |
| OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR |
| CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE |
| REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| CODE, BUILDING . |
| 805.3 EXIT SIGNS. MEANS OF EGRESS FROM THE HIGHEST WORK |
| AREA FLOOR TO THE FLOOR OF EXIT DISCHARGE SHALL BE |
| PROVIDED WITH EXIT SIGNS IN ACCORDANCE WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING . |
| |
| 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |