Plan Review Notes For Permit 11030368 |
Permit Number |
11030368 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-03-17 11:49:31 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. SEE OPENING 1, ALTHOUGH 7.5 IS HIGHLIGHTED ON | | PRODUCT APPROVAL, 7.5" REQUIRED FOR CONDITIONS STATED, | | BUT ON THE INSTALLATION SCHEDULE16" IS PROPOSED FOR | | ANCHOR SPACING FOR BOTTOM, C2 CONNECTION TYPE. PLEASE | | REVISE AND CHECK ALL OPENINGS, ESPECIALLY BOTTOM | | CONNECTIONS WITH BLOCK SUBSTRATE. | | | | PLEASE BE ADVISED THAT, IN THE FUTURE, PERMITS MAY BE | | ISSUED WITH PROVISO THAT NON COMPLIANT PERMIT DOCUMENTS | | BE SUBMITTED AS A REVISION (WITH FEES). | | | | |
|