Plan Review Notes
Plan Review Notes For Permit 11030281
Permit Number 11030281
Review Stop B
Sequence Number 1
Notes
Date Text
2011-03-23 13:40:50****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE
 PROPOSED WORK, INCLUDING SIZE OF THE AWNING.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB.
  
 3. PLEASE ADVISE, HOW HAS THE STRUCTURAL INTEGRITY OF
 THE EXISTING AWNING BEEN DETERMINED? I WAS UNABLE TO
 LOCATE A PERMIT FOR THE AWNING. OUR COMPUTERIZED SYSTEM
 HAS RECORDS FROM 1998 TO PRESENT. IF THE AWNING WAS
 INSTALLED WITHOUT A PERMIT, PROVIDE ENGINEERING. IF IT
 WAS INSTALLED WITH A PERMIT PRIOR TO 1998, PROVIDE MORE
 INFORMATION.
  
 4. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
  