2011-03-22 16:15:13****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. CLARIFY SCOPE. APPLICATION IS FOR DOORS AND
 SHUTTERS, PLAN SHOWS DUMPSTER ENCLOSURE AND CANOPY, AND
 CANOPY PRODUCT APPROVAL WAS SUBMITTED. REMOVE
 UNNECESSARY DETAILS FROM THE PLAN OR REVISE THE
 APPLICATION.
  
 2. DETAIL FOR "EXISTING STOREFRONT TO BE PROVIDED WITH
 ACCORDION SHUTTERS" DOES NOT CORRELATE WITH THE SITE
 PLAN.
  
 3. PLAN SHOWS THAT A 4' DOOR WILL REPLACE A 3' EXISTING
 DOOR, PROVIDE A STRUCTURAL DETAIL FOR THE ENLARGED
 OPENING.
  
 4. PROVIDE THE PRODUCT APPROVAL COVER SHEET FOR THE
 ACCORDION SHUTTERS.
  
 5. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 6. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 5 ABOVE. FBC R301, FBC1609,
 FBC*106.
  
 7. IT APPEARS THAT THIS APPLICATION PROPOSES COVERING
 EXIT DOORS WITH ACCORDION SHUTTERS. SEE FBC 1003.6,
 MEANS OF EGRESS CONTINUITY. THE PATH OF EGRESS TRAVEL
 ALONG A MEANS OF EGRESS SHALL NOT BE INTERRUPTED BY ANY
 BUILDING ELEMENT OTHER THAN A MEANS OF EGRESS COMPONENT
 AS SPECIFIED IN THIS CHAPTER.
  
  
  