Plan Review Notes
Plan Review Notes For Permit 11030268
Permit Number 11030268
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-03-09 12:00:482727 GEORGIA AVENUE
 PERMIT #11030268
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 A SMOKE DETECTOR HAS NOT BEEN PROVIDED IN CLASSROOM 7.
  
 NOTIFICATION APPLIANCES ARE NOT SHOWN ON ANY OF THE
 INTERIOR ROOMS.
  
 UPDATE RISER DIAGRAM AND BATTERY CALCULATIONS TO
 INCLUDE ALL INITIATING DEVICES AND NOTIFICATION
 APPLIANCES.
  
 RISER DIAGRAM ONLY SHOWS ONE DEDICATED TELEPHONE LINE.
  
 FIRE ALARM NOTE 16 AND NOTE 17 MAKE REFERENCE TO A
 SPRINKLER SYSTEM TAMPER SWITCH AND DUCT SMOKE
 DETECTORS. VERIFY THESE NOTES ARE APPLICABLE TO THIS
 PROJECT.
  
 FIRE ALARM NOTE 20 REFERENCES SECURITY LOCKS TO BE
 INTERFACED WITH THE FIRE ALARM SYSTEM. PLEASE PROVIDE
 ADDITIONAL INFORMATION.
  
 KITCHEN HOOD SUPPRESSION SYSTEM TO BE TIED INTO FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  