2011-03-15 10:00:43TUESDAY 3/15/ 2011
 BUILDING PLAN REVIEW
 PERMIT: 11030179
 ADD: 205 CLEMATIS ST
 CONT: BSA CORP.
 TEL: (561)272-6350
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) INTERIOR DEMO ONLY, THIS PERMIT INDICATES THE
 CUTTING AND SHORING OF STRUCTURAL COMPONENTS. THE
 EXISTING AND PROPOSED OCCUPANCY WILL BE A THEATER WITH
 A OCCUPANT LOAD GREATER THAN 500, CREATING A THRESHOLD
 BUILDING PER FL S 553.71(7) AN ASSEMBLY OCCUPANCY,
 BUILDING GREATER THAN 5,000 SQ FT AND OCCUPANT LOAD OF
 GREATER THAN 500 PERSONS.
  
 1A) WILL NEED A WRITTEN THRESHOLD REPORT BEFORE
 ISSUANCE OF PERMIT.
  
 1B) WILL NEED A SPECIAL INSPECTOR SIGNED ON BEFORE
 ISSUANCE OF PERMIT.
  
 NOTE STRUCTURAL SHEETS INDICATE THEY ARE IN PROGRESS
 DRAWINGS/ NOT A COMPLETE DESIGN!
 DOUG WISE & MYSELF CALLED ONM&J.
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 ----------------------------------------------------
  
  
 MONDAY/ 3/21/2011
 BUILDING PLAN REVIEW
 PERMIT: 11030179
 ADD: 205 CLEMATIS ST
 CONT: BSA CORP.
 TEL: (561)272-6350
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2007 FBC-B 1025.4
 1025.4 FOYERS AND LOBBIES. IN GROUP A-1 OCCUPANCIES,
 WHERE PERSONS ARE ADMITTED TO THE BUILDING AT TIMES
 WHEN SEATS ARE NOT AVAILABLE AND ARE ALLOWED TO WAIT IN
 A LOBBY OR SIMILAR SPACE, SUCH USE OF LOBBY OR SIMILAR
 SPACE SHALL NOT ENCROACH UPON THE REQUIRED CLEAR WIDTH
 OF THE MEANS OF EGRESS. SUCH WAITING AREAS SHALL BE
 SEPARATED FROM THE REQUIRED MEANS OF EGRESS BY
 SUBSTANTIAL PERMANENT PARTITIONS OR BY FIXED RIGID
 RAILINGS NOT LESS THAN 42 INCHES (1067 MM) HIGH. SUCH
 FOYER, IF NOT DIRECTLY CONNECTED TO A PUBLIC STREET BY
 ALL THE MAIN ENTRANCES OR EXITS, SHALL HAVE A STRAIGHT
 AND UNOBSTRUCTED CORRIDOR OR PATH OF TRAVEL TO EVERY
 SUCH MAIN ENTRANCE OR EXIT.
  
 1A) A NEW LS-1 SHEET WAS SUBMITTED FRIDAY MARCH 18/
 2011. THE OCCUPANT LOAD ANALYSIS UNDER THE REALISTIC
 LOAD DOES NOT INCLUDE LOADS
 FROM A FIRST FLOOR CONCENTRATED LOBBY TO BE INCLUDED IN
 THE TOTAL LOAD COUNT. SECTION 1025.4 MAKES THE
 STIPULATION THAT THE WAITING AREAS SHALL BE SEPERATED
 BY PARTITION OR FIXED RIGID RAILS. IN THE AI OCCUPANCY
 TYPE THE CODE IS CLEAR THE LOBBY AREA IS TO BE
 CONSIDERED AS PART OF THE TOTAL OCCUPANT LOAD SINCE
 MANY TIMES A SHOW MAY BE EXITING WHILE THE LOBBY IS
 FULL AND STAGED FOR THE NEXT SHOW. WITHIN THTE STAGING
 AREA DOORS SHOULD BE DESIGNATED FOR THESE OCCUPANTS IN
 CASE OF EMERGENCY. YOU MAY DEDUCT THE CLEAR EGRESS PATH
 FOR THE PATRONS EXITING THE THEATER.
 I CALCULATED FOR THE FIRST FLOOR 76'X5'=380 SQ FT/ 7=
 55 OCCUPANTS DROPPING THE FIRST FLOOR LOBBY FROM 235 TO
 180. EVEN WITH THIS DEDUCTION TTHE OCCUPANCY LOAD STILL
 IS OVER 500 AT 571 ( THIS IS USING THE 25 OCCUPANT LOAD
 FOR THE STAGE AND NOT MAXIMUM OF 76). THIS OCCUPANT
 LOAD WILL STILL BY DEFINTION CREATE THRESHOLD
 REQUIREMENTS BY FL S 553.71(7).
 FL S 553.71(7)
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
 3/29/11
 E-MAIL SENT :
 TO: BILL BRANNING
 CC: DOUG WISE & MIKE CARSILLO
 GOOD MORNING BILL,
 I'VE TAKEN THE LETTER WRITTEN BY THE MANAGING DIRECTOR
 AND COVER SHEET SUBMITTED BY THE DESIGN TEAM ZEIDER
 PARTNERSHIP INC. ARCHITECTS TO THE BUILDING OFFICIAL
 DOUG WISE AND FIRE CHIEF MIKE CARCILLO TO DISCUSS THE
 OCCUPANT LOADING OF THE FOYER/ LOBBY (PRE-FUNCTION
 AREA) FOR THE PALM BEACH DRAMAWORKS. IF THE
 PRE-FUNCTION OCCUPANT LOAD SHOULD OR SHOULD NOT BE
 TAKEN INTO ACCOUNT AS PART OF THE TOTAL OCCUPANT LOAD
 FOR THIS BUILDING. ALL AGREE THE CODE AND CODE
 COMMENTARY INDICATE IN 2007/2009 FBC-B 1025.4 THE
 OCCUPANT LOAD OF THE PRE-FUNCTION AREA IS TO BE TAKEN
 INTO ACCOUNT OF THE TOTAL OCCUPANT LOAD THIS WILL PUT
 YOU WELL OVER 500 OCCUPANTS.
  
 BY DEFINITION THIS IS A THRESHOLD BUILDING (FS
 553.71(7) WHICH WILL REQUIRE A WRITTEN THRESHOLD REPORT
 (2007FBC-B 109.3.6) AND ASPECIAL INSPECTOR.
  
 BILL YOU WILL PROBABLY WANT TO SET UP A MEETING WITH
 ALL YOUR INTERESTED PARTIES DOUG WISE, MIKE CARSILLO
 AND MYSELF TO DISCUSS THIS MATTER SO WE CAN ISSUE BOTH
 THE INTERIOR DEMO AND INTERIOR REMODEL PERMITS. DOUG
 WILL NOT BE AVAILABLE TO MEET WITH YOU UNTIL LATER IN
 THE DAY, (LATE PM) FRIDAY APRIL 1ST.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731