2011-03-15 09:25:37PLANS DENIED
 HOOD AND WALK IN COOLERS MUST HAVE SEPARATE PLANS
 ,PERMIT AND APPLICATION.
 CONDENSATE DRAIN FOR THREE TON A/C CAN NOT TIE IN TO
 WASTE WATER SECTION 90-125 CITY CODE.
 REFER TO SECTION 606.2.1 SUPPLY AIR 2007 FBC (M) SMOKE
 DETECTORS SHALL BE INSTALLED ON SUPPLY.
 REFER TO SECTION 606.3 INSTALLATION 2007 FBC (M) .
 PLEASE PROVIDE THE LENGTH OF TEK SCREW FOR RTU MOUNTING
 DETAIL.
 PLEASE PROVIDE A DETAIL FOR CURB TO ROOF TIE DOWN.